INSTALLATION
COMMISSIONING
Fitting the collector sensor
1
3
5
4
2
2
6
_0
3_0
1
_0
1
9
2
1 Heat conducting paste
2 Temperature sensor
3 Sensor well
4 Thermal insulation
5 Flow direction of the heat transfer medium
Sensor resistance values
The sensors integrated in the appliance, the sensors provided and
the outside temperature sensor are PTC sensors. The collector
sensor is a PT 1000 sensor.
PTC sensor resistance values
Temperature in °C
Resistance in Ω
– 20
1367
– 10
1495
0
1630
10
1772
20
1922
25
2000
30
2080
40
2245
50
2417
60
2597
70
2785
80
2980
90
3182
100
3392
PT 1000 sensor resistance values
Temperature in °C
Resistance in Ω
– 30
843
– 20
922
– 10
961
0
1000
10
1039
20
1078
30
1117
40
1155
50
1194
60
1232
70
1271
80
1309
90
1347
100
1385
110
1423
120
1461
!
When measuring with a multimeter, the resistance
values serve only to identify faulty or incorrect
sensors. Measuring with a multimeter is too imprecise
to test for accuracy.
11. Commissioning
!
Only approved contractors may commission this
equipment and instruct the operator in its use.
»
Commission the system in accordance with these operating
and installation instructions. Our customer service can provide
commissioning support, which is chargeable.
11.1 Checks before commissioning
Ventilation system
— Have the air ducts been installed and insulated correctly?
Cylinder
— Has the cylinder been filled (hot tap open until water flows
out)?
— Has a pressure reducing valve been installed if the water
pressure is above 5 bar?
Temperature sensor
— Have all temperature sensors been correctly placed and
connected?
!
Operating the ventilation appliance is not permitted
whilst building work is still in progress.