INsTALLATIoN
Specification
www.stiebel-eltron.com
LWZ 130 |
51
EN
GL
ISH
17.4 Data table
LWZ 130
LWZ 130 Enthalpie
237805
237806
Sound emissions
Sound power level with standard ventilation and 50 Pa external dB(A)
33
33
Sound power level (EN 12102)
dB(A)
33
33
Application limits
Application range, outdoor air (temperature)
°C
-15-40
-15-40
Application range, extract air (temperature)
°C
15-35
15-35
Energy data
Energy efficiency class
A
A
Electrical data
Rated voltage
V
230
230
Phases
1/N/PE
1/N/PE
Frequency
Hz
50
50
Power consumption incl. preheating coil
A
5
5
Power consumption excl. preheating coil
A
0.46
0.46
Max. power consumption
W
87.9
71
Power consumption incl. preheating coil
W
1150
1150
Power consumption excl. preheating coil
W
105
105
Max. mains impedance Zmax
Ω
0.32
0.32
Versions
Filter class
ePM10 ≥ 50 % (M5) | ISO Coarse > 60 % (G4) ePM10 ≥ 50 % (M5) | ISO Coarse > 60 % (G4)
IP rating
IP20
IP20
Dimensions
Height
mm
248
248
Width
mm
520
520
Depth
mm
1113
1113
Weights
Weight
kg
18
18
Connections
Air connector diameter
mm
125
125
Condensate connection
mm
16.5
16.5
Values
Heat recovery level up to
%
87
87
Air flow rate
m³/h
50-180
50-180
Min. ambient conditions, installation room (temperature)
°C
2
2
Max. ambient conditions, installation room (temperature)
°C
35
35
Storage and transport temperature
°C
50
50
Available external pressure at max. air flow rate
Pa
160
160
Heat recovery level
%
87
87
Further details
LWZ 130
LWZ 130 Enthalpie
237805
237806
Maximum altitude for installation
m
2000
2000
326794-41212-9444_LWZ_130_de_en.indb 51