INSTALLATION
Maintenance and cleaning
26
0
4
01
0
57
5
f
f
Remove the dirt grille arranged above the condensate pan by
pushing it together from its sides and remove it upwards.
f
f
Check the defrost pan drain and clean it, if required.
26
0
4
01
0
57
7
Beneath the evaporator is a two-part evaporator gasket. The two
parts of the gasket are held together with a bracket.
f
f
Pull the bracket upwards to remove.
f
f
Initially, remove the l.h. half of the evaporator cover.
26
0
4
01
0
59
1
f
f
Then remove the r.h. half of the evaporator cover.
!
Material losses
Do not use any cleaning agents, just water.
!
Material losses
Do not use a high pressure cleaner otherwise the evap-
orator fins may be bent.
f
f
Spray water across the evaporator fins.
f
f
Remove the water from the appliance using a wet suction
device.
f
f
Remove contaminants and blockages.
Note
Check the condensate drain regularly, at least once a year.
10.4 Cleaning the condensate drain
Check the condensate drain regularly.
f
f
Remove the evaporator cover (see chapter "Cleaning the
evaporator fins").
f
f
Remove dirt and blockages immediately.
f
f
To test the drain, pour one litre of water, for example from
two half-litre bottles, into the condensate pan.
If the condensate pan does not overflow, the drainage facility is
adequate.
10.5 Cleaning the filter ball valve
26
0
4
01
0
61
4
f
f
Close the filter ball valve by turning it 90° clockwise.
f
f
Undo the cap.
f
f
If the filter element is contaminated, connect a short hose for
backwashing.
f
f
Place the free end of the hose in a bucket.
f
f
Turn the filter ball valve 15° clockwise.
f
f
Turn the filter ball valve 15° back again.
f
f
Check whether cleaning was successful. Repeat backwashing
if required.
f
f
Refit the cap.
f
f
Open the filter ball valve by turning it 90° anti-clockwise.
f
f
Check the system fill pressure and adjust if required.