8. Maintenance
WARNING Electrocution
Disconnect the appliance from the power supply before
carrying out work inside the appliance.
Activity
Maintenance inter-
val (in years)
Cleaning the heat exchanger and condensate pan
1
Condensate drain
1
Air ducts
3
8.1
Cleaning the heat exchanger and condensate
pan
f
Open the appliance cover. See chapter "Opening the appli-
ance cover" in the operating instructions.
VRL-C 300:
3
D
00000
9
6
5
3
4
4
2
1
6
5
7
1 Heat exchanger
2 Reheating coil (not installed in some appliances)
3 Fixing screws for heat exchanger retainer
4 Condensate pan fixing screws
5 Condensate pan
6 Condensate pan fixing screws
7 Mounting bracket for heat exchanger
VRL-C 6 25, VRL-C 870:
3
D
00000
9
6
5
3
4
4
6
1
6
5
2
1 Heat exchanger
2 Reheating coil (not installed in some appliances)
3 Fixing screws for heat exchanger retainer
4 Condensate pan fixing screws
5 Condensate pan
6 Mounting bracket for heat exchanger
f
Undo the fixing screws for the heat exchanger retainer.
f
Pull the heat exchanger retainer down and out.
f
Undo the fixing screws of the condensate pan.
!
Material losses
f
Remove the condensate pan from the appliance
carefully as it may still contain water.
f
VRL-C 300: Undo the fixing screws at the end of the conden-
sate pan.
f
VRL-C 6 25, VRL-C 870: The condensate pan is pushed hori-
zontally on to a bolt on the exhaust air fan side. Carefully pull
the condensate pan towards the heat exchanger.
f
Carefully tilt the condensate pan down and pull the conden-
sate pan towards the heat exchanger.
f
Remove the condensate pump float from its retainer in the
condensate pan.
f
Remove the condensate pan from the appliance.
f
Carefully clean the condensate pan with lukewarm water.
!
CAUTION Injury
The heat exchanger weighs approx. 20 kg.
f
During removal, take the weight of the heat ex-
changer into consideration.
f
Use suitable load-handling equipment.
!
Material losses
When removing and cleaning the heat exchanger, take
care not to damage the heat exchanger fins.
f
Undo the fixing screws for the reheating coil.
!
Material losses
Never expose the reheating coil wiring to any tensile load.
f
Never allow the reheating coil to hang by the wiring.
f
VRL-C 300: Undo the screws on the heat exchanger mounting
brackets.
f
VRL-C 6 25, VRL-C 870: Undo the screws on the heat exchang-
er mounting bracket.
f
To install the heat exchanger with the same orientation at a
later time, mark the installation position of the heat exchang-
er before removing it.
f
Carefully remove the heat exchanger from the unit. Do not let
it fall.
f
Use a commercially available vacuum cleaner to remove dust
and other loose dirt particles from the intake and discharge
surfaces.
f
If required, clean the heat exchanger with warm water
(max. 55 °C) and a commercially available detergent. Do not
use solvents.
f
Flush the heat exchanger with water.
f
Allow the heat exchanger to dry completely.