1. Notes on Safety
1
1
NOTES ON SAFETY
To prevent avoidable problems from occurring during commissioning and/or operation, it is essential to
read and comply with this entire instruction manual before starting installation and commissioning.
Based on DIN EN 50178 (once VDE 0160), FBS/FDS-series frequency inverters are defined as electronic
power equipment (BLE) for the control of power flow in high-voltage systems. They are designed exclusively to
power three-phase-current, asynchronous machines. Handling, installation, operation and maintenance must be
performed in accordance with valid and/or legal regulations, applicable standards and this technical
documentation.
The frequency inverter are products of the restricted sales class (in accordance with IEC 61800-3. Use of this
products in residential areas may cause high-frequency interference in which case the user may be ordered to
take suitable measures.
The user must ensure strict adherence to these standards.
The safety notes and specifications stated in additional sections (items) must be adhered to by the user.
Caution! High touch voltage! Danger of electric shock! Danger of death!
Never under any circumstances may the housing be left open or connections disconnected when the power is
on. Disconnect the power plug of the frequency inverter and wait at least 5 minutes after the power voltage has
been switched off before opening the frequency inverter to install or remove option boards. Correct configuration
and installation of the inverter drive are prerequisites to correct operation of the frequency inverter. Only
appropriately qualified personnel may transport, install, commission and operate this device.
The frequency inverter must be installed in a switching cabinet which does not exceed the maximum ambient
temperature (see technical data).
Only copper wiring may be used. For use in the U.S.A., see table 310-16 of the National Electrical Code (NEC)
for line cross sections to be used at 60 °C or 75 °C.
STÖBER ANTRIEBSTECHNIK accepts no liability for damages caused by non-adherence to the
instructions or applicable regulations.
The motor must have an integral temperature monitoring device or external motor overload protection must be
used.
Only suitable for use on power networks which cannot supply more than a symmetric, nominal short-circuit
current of 5000 A at 240 V ac / 480 V ac.
Notes:
Subject to technical changes for improvement of the devices without prior notice. This documentation
is solely a product description. It is not a promise of features in the sense of warranty rights.
Pay particular attention to the following:
•
Permissible protection class: Protective ground; operation only permitted when protective
conductor is correctly connected. The devices may not be operated directly on IT networks.
•
Installation work may only be performed in a voltage-free state. When work has to be done on the drive,
inhibit the enable and disconnect the complete drive from the power network. Adhere to the 5 safety
regulations.
•
Discharge time of the DC link capacitors > 5 minutes
•
Do not penetrate the interior of the device with any kind of object.
•
When performing installation or other work in the switching cabinet, protect the device against falling
objects (e.g., pieces of wire, flexible leads, metal parts and so on). Conductive parts may cause short
circuiting or device failure on the frequency inverter.
•
Before commissioning, remove all extra coverings to prevent the device from overheating.