13. Parameter Description
P
Speed depends on pole number
B10
; f
max
= 400 Hz. With a 4-pole motor, this is 12000 rpm at 400 Hz.
•
The power pack must be turned off before these parameters can be changed.
Italics
These parameters are sometimes not shown depending on which parameters are set.
1)
See result table in chap. 15.
2) Only available when
D90
≠
1
Parameters which are included in the
normal
menu scope (
A10
=0). For other parameters, select
A10
=
1:extended
or
A10
=
2:service
.
Parameters marked with a "
√
" can be parameterized separately from each other in parameter record 1 and 2.
37
E.. Display Values
Para. No. Description
E54
Option-board:
Indication of the option board detected during initialization.
0: none;
No option board or external 24 V power supply missing.
1: GB 4000;
3: 24 V supply;
5: SSI 4000;
7: EA 4001;
2: EA 4000;
4: ASI 4000;
6: GB 4001;
E55
Identity-number:
Number assigned by the user as desired from 0 to 65535. Can only be write-accessed with
FDS Tool or fieldbus.
E56
Parameter set ident. 1:
Indicates whether parameters in parameter record 1 were changed. Can be used to detect
unauthorized manipulation of parameters. The parameter record ID does not change when the actions “
B40
phase test” and
“
B41
autotuning” are executed.
0:
all values are default settings (
A04
=1).
1:
Specified value during initialization by FDS Tool.
2 to 253:
Customer specification/configuration with FDS Tool. Status without change.
254:
When parameters are changed via fieldbus or via the USS protocol,
E56
and
E57
= 254 are set.
255:
At least one parameter value was changed with the keyboard (Controlbox or device).
E57
Parameter set ident. 2:
Same as
E56
but for parameter set 2.
E58
Kommubox:
Type of Kommubox for fieldbus communication which is installed on X3 and was automatically
detected.
E60
Reference value selector:
Indicates the result of the binary
coding of the fixed reference values. Selection is binary via
inputs BE1 to BE5. At least one binary input must be
parameterized for the reference value selector (
F3..
=1 to 3).
The result of the binary coding is indicated with the digits 0
to 7. A fixed reference value/ramp record is assigned to this
result.
A fixed reference value can also be specified directly with
D09
. However,
E60
is not affected by
D09
. In position mode
(
C60
=2),
E60
indicates the result of process block
specification with binary inputs (
E60
=0
→
proc. block1).
E61
Additional ref. value:
Current additional reference value to be added to the reference value being used. Can
come from AE2 (
F20
=1), AE1 (
F25
=1) or the fieldbus. See block circuit diagram in chap. 19.
E62
Actual M-max:
Currently effective M-Max as a minimum from M-Max 1 (
C03
), M-Max 2 (
C04
), and the torque
resulting from the level on AE2, if the AE2 function is parameterized for torque limit (
F20
=2) or power limit
(
F20
=3) or is from the fieldbus.
E63
PID-controller limit:
Only if
G00
=1 (i.e., PID controller is active).
0: inactive;
1: active;
The PID controller output is limited to
G04
or
G05
.
E65
PID control deviation:
Difference between analog input 2 signal after smoothing, offset and factor and
E121
PID reference.
E71
AE1 scaled:
AE1 signal after offset and factor.
E71
= (
E10
+
F26
) *
F27
. Cf. block circuit diagram in chap. 19.
E72
AE2 scaled:
AE2 signal after offset and factor.
E72
= (
E11
+
F21
) *
F22
E73
AE2 scaled 2:
AE2 signal after smoothing, offset and factor as well as PID controller and offset 2.
E72
= ( PID ( (
E11
+
F21
) *
F22
) ) +
F24
. Cf. block circuit diagram in chap. 19.
E80
Operating condition:
Indicates the current operating state as shown by the operational display. Cf. chapter 16
(operating states). Useful for fieldbus poling or serial remote control.
E81
Event level:
Indicates whether a current event is present. The type of event is indicated in
E82
. Useful for
fieldbus poling or serial remote control.
0: inactive;
No event is present.
1: message;
2: warning;
3: fault;
E82
Event name:
Indicates the current event/fault. Cf. chap. 17. Useful for fieldbus poling or serial remote control.
E83
Warning time:
The time remaining until the fault is triggered is indicated for the active warnings. This time can
be changed via FDS Tool. Useful for fieldbus poling or serial remote control.
E84
Active parameter set:
Indicates the current parameter record. Cf. chapter 9.4. Useful for fieldbus poling or
serial remote control.
1: parameter set 1;
2: parameter set 2;
E100
Parameters
E100
and above are used to control and parameterize the inverters by fieldbus. For details, see the
documentation of your fieldbus system.
RV select
2 1 0
E60
Reference
Value
Proc.
Block
0
0
0
0
Analog, freq,..
1
0
0
1
1
Fix. ref. val. 1
2
0
1
0
2
Fix. ref. val. 2
3
0
1
1
3
Fix. ref. val. 3
4
1
0
0
4
Fix. ref. val. 4
5
1
0
1
5
Fix. ref. val. 5
6
1
1
0
6
Fix. ref. val. 6
7
1
1
1
7
Fix. ref. val. 7
8