13. Parameter Description
P
Depends on pole number
B10
; f
max
= 400 Hz. With a 4-pole motor:, this is 12000 rpm at 400 Hz.
•
The power pack must be turned off before these parameters can be changed.
Italics
These parameters are sometimes not shown depending on which parameters are set.
1)
See result table in chap. 15.
2) Only available if
D90
≠
1
Parameters which are included in the
normal
menu scope (
A10
=0). For other parameters, select
A10
=1:
extended
or
A10
=2:
service
.
Parameters marked with a "
√
" can be parameterized separately from each other in parameter record 1 and 2.
54
U.. Protective Functions
Para. No. Description
U32
Text acceleration overload:
The entry "acceleration overload" can be varied to suit user-specific requirements.
Value range:
0 to ”acceleration overload” to 11
U40
Level break overload:
If the calculated torque exceeds the current M-Max in
E62
during the deceleration ramp,
U40
is triggered.
0: off;
device does not react when
U40
is triggered.
1: message;
triggering of
U40
is only indicated. The device continues to be ready for operation.
2: warning;
after expiration of the tolerance time in
U41
, the device assumes fault mode (for E49, see chap. 17).
3: fault;
the device immediately assumes fault mode (for E49, see chap. 17) after
U40
is triggered.
U41
Time break overload:
Can only be set with
U40
=2:
warning
. Defines the time during which an overload of the
drive during deceleration is tolerated. After expiration of the set time, the device assumes fault mode.
Value range in sec:
1 to 5 to 10
U42
Text break overload:
The entry "break overload" can be varied to suit user-specific requirements.
Value range:
0 to ”break overload ” to 11
U50
Level operating range
If one or more of the parameters
C41
to
C46
are violated,
U50
is triggered.
0: off;
device does not react when
U50
is triggered.
1: message;
triggering of
U50
is only indicated. The device continues to be ready for operation.
2: warning;
after expiration of the tolerance time in
U51
, the device assumes fault mode (for E50, see chap. 17).
3: fault;
the device immediately assumes fault mode (for E50, see chap. 17) after
U50
is triggered.
U51
Time operating range:
Can only be set with
U50
=2:
warning
. Defines the time tolerated outside the work area.
After expiration of the set time, the device assumes fault mode.
Value range in sec:
1 to 10 to 120
U52
Text operating range:
The entry ”operating range” can be varied to suit user-specific requirements.
Value range:
0 to ”operating range” to 11
U60
Level following error:
If the value in
I84
exceeds the value of
I21
,
U60
is triggered.
0: off;
device does not react when
U60
is triggered.
1: message;
triggering of
U60
is only indicated. The device continues to be ready for operation.
2: warning;
after expiration of the tolerance time in
U61
, the device assumes fault mode (for E54, see chap. 17).
3: fault;
the device immediately assumes fault mode (for E54, see chap. 17) after
U60
is triggered.
U61
Time following error:
Can only be set with
U60
=2:
warning
. Defines the time during which the value in
I21
is
exceeded. After expiration of the set time, the devices assumes fault mode.
Value range in msec:
0 to 500 to 32767
U70
Level posi. Refused:
If the target position is located outside software stops
I50
and
51
or an absolute process
block is started in an unreferenced state (
I86
=0),
U70
is triggered.
0: off;
device does not react when
U70
is triggered.
1: message;
triggering of
U70
is only indicated. The device continues to be ready for operation.
2: warning;
after expiration of the tolerance time of 1 sec, the device assumes fault mode (for E51,
see
chap. 17).
3: fault;
the device immediately assumes fault mode (for E51, see chap. 17) after
U70
is triggered.