Installation
ID 442269.07
40
Projecting manual POSIDRIVE® FDS 5000
4
WE KEEP THINGS MOVING
4
Installation
This chapter will give you information about installation. This includes:
•
Installation of the inverter in the switching cabinet
•
Installation of accessories on or in the inverter
WARNING!
Danger of personal injury and material damage due to electric shock!
Always switch off all power supply voltage before working on the inverter! Note that the discharge time of
the DC link capacitors is up to 5 minutes. You can only determine the absence of voltage after this time
period.
4.1
Installation of the inverter in the switching cabinet
NOTICE
Danger of property damage from incorrect installation of the devices!
It is essential to comply with the following installation instructions to avoid damage to the devices.
•
The inverters must be installed in a control cabinet with at least protection class IP54.
•
The installation location must be free of dust, corrosive vapors and all fluids (in accordance with pollution
degree 2 as per EN 60204/EN 50178).
•
The installation location must be free of atmospheric moisture.
•
Prevent condensation, for example with anti-condensation heating elements.
•
For reasons related to EMC, use mounting plates with a conductive surface (unpainted, etc.).
•
Fasten the inverters onto the mounting plate with M5 screws.
•
The inverters must be installed vertically: