52
6.3.8 COMPRESSOR STARTS AND RUNS, BUT SHORT CYCLES ON OVERLOAD
PROTECTOR
CAUSE
CORRECTION
Low voltage to unit ........................................................ Determine reason and correct.
Improperly wired ........................................................... Check wiring against diagram.
Overload protector defective ......................................... Replace overload protector.
Capacitor defective ....................................................... Check start/run capacitor. Replace if defective.
Excessively high discharge pressure ............................ *Refer to Troubleshooting Subsection 6.3.18.
Compressor too hot ...................................................... *Refer to Troubleshooting Subsection 6.3.19.
Excessively low suction pressure ................................. *Refer to Troubleshooting Subsection 6.3.21.
Excessively high suction pressure ................................ *Refer to Troubleshooting Subsection 6.3.20.
Compressor motor has shorted .................................... *Replace compressor.
6.3.9 COMPRESSOR START CAPACITOR OPEN, SHORTED OR BLOWN
CAUSE
CORRECTION
Loose wires. .................................................................. Locate and correct.
Start relay failure. .......................................................... Replace start relay.
Excessively short cycling. ............................................. Determine reason and correct.
Improper capacitor. ....................................................... Determine correct size and replace.
Prolonged operation on start cycle due to low
voltage to unit. ............................................................... Refer to Troubleshooting Subsection 6.3.7.
6.3.10 COMPRESSOR RUN CAPACITOR OPEN, SHORTED OR BLOWN
CAUSE
CORRECTION
Excessively high line voltage (110% of rated
max.). ............................................................................ Contact your local power company.
Improper capacitor. ....................................................... Determine correct size and replace.
Compressor relay incorrectly mounted. ........................ Remount relay in correct position.
6.3.11 COMPRESSOR START RELAY DEFECTIVE OR BURNED OUT
CAUSE
CORRECTION
Incorrect start relay. ...................................................... Check and replace.
Incorrect mounting angle. ............................................. Remount relay in correct position.
Line voltage too high or too low (± 10%). ..................... Contact your local power company.
Excessively short cycling. ............................................. Determine reason and correct.
Relay being influenced by loose vibrating
mounting. ...................................................................... Remount rigidly.
Incorrect run capacitor. ................................................. Replace with proper capacitor.
6.3.12 COMPRESSOR WILL NOT RUN, BUT DRIVE MOTOR RUNS
CAUSE
CORRECTION
Normal barrel stir cycle. ................................................ No correction required.
Power module defective. .............................................. Replace power module.
8-Pin relay defective. .................................................... Replace 8-pin relay. (E131 & F131 only)
Compressor contactor defective. .................................. Replace contactor.
Program module defective. ........................................... Replace program module.
Compressor problem. ................................................... Refer to Troubleshooting Subsection 6.3.5 through 6.3.11.
Summary of Contents for E131G
Page 1: ...Model E131G F131G SERVICE MANUAL Manual No 513537 3 Mar 2004...
Page 2: ......
Page 14: ...6...
Page 38: ...30 Figure 51 Power Board...
Page 39: ...31 Figure 52 Program Module...
Page 54: ...46...
Page 66: ...58...
Page 68: ...60...
Page 69: ...61 666786...
Page 70: ...62...
Page 71: ...63...
Page 72: ...64...
Page 73: ...65...
Page 74: ...66...
Page 75: ...67...
Page 76: ...68...
Page 77: ...69...
Page 78: ...70...
Page 80: ......