54
6.3.16 FREEZER WILL NOT LEAVE PRESENT MODE
CAUSE
CORRECTION
Loose or defective touch pad connection. .................... Repair the touch pad connection.
6.3.17 TOUCH PAD LIGHTS DO NOT WORK: FREEZER OPERATES NORMALLY
CAUSE
CORRECTION
Touch pad defective ..................................................... Replace touch pad.
Loose or improper connections to the touch pad ......... Check and repair the touch pad connections.
Control logic board is defective .................................... Replace control logic board.
6.3.18 COMPRESSOR DISCHARGE PRESSURE TOO HIGH
CAUSE
CORRECTION
Improper freezer air clearance ...................................... Remove airflow restrictions. Maintain adequate clearances.
Freezer located near heat source ................................. Move or direct hot air away from freezer.
Ambient temperature is high ......................................... Same as above.
Freezer discharge air recirculating into
condenser intake .......................................................... Eliminate recirculating using Stoelting top rear air discharge
...................................................................................... plenum.
Dirty condenser and/or filter .......................................... *Clear condenser.
Entering water temperature to water-cooled
Condenser is excessively high ..................................... Determine cause and correct.
Condenser fan and/or fan motor is defective ................ Replace fan and/or fan motor.
Discharge line, condenser tube, or condenser
U-bend restriction (especially in top half of
condenser) .................................................................... *Repair restriction.
Water valve out of adjustment ...................................... Make appropriate adjustment. Refer to Refrigeration Section 4
...................................................................................... Subsection 4.22.
Dirt or restriction on waterside of water-cooled
condenser or connecting water lines ............................ Flush condenser and lines thoroughly.
Refrigerant overcharge ................................................. *Recover charge. Evacuate and recharge per nameplate by
...................................................................................... weight-ounces.
Air or noncondensable gases in refrigeration
system ........................................................................... *Same as above.
6.3.19 COMPRESSOR RUNNING TOO HOT: TRIPS ON OVERLOAD PROTECTOR
CAUSE
CORRECTION
Excessively high discharge pressure ............................ Refer to Troubleshooting Subsection 6.3.18.
Suction line insulation loose or missing ........................ Re-insulate suction lines.
Expansion valve setting grossly out of
adjustment .................................................................... *Replace expansion valve.
NOTE
Expansion valve setting is preset for optimum balance of flow to barrel and hopper-
DO NOT ATTEMPT TO ADJUST THE VALVE SETTING.
Internal mechanical trouble in compressor ................... *Replace compressor.
Summary of Contents for E131G
Page 1: ...Model E131G F131G SERVICE MANUAL Manual No 513537 3 Mar 2004...
Page 2: ......
Page 14: ...6...
Page 38: ...30 Figure 51 Power Board...
Page 39: ...31 Figure 52 Program Module...
Page 54: ...46...
Page 66: ...58...
Page 68: ...60...
Page 69: ...61 666786...
Page 70: ...62...
Page 71: ...63...
Page 72: ...64...
Page 73: ...65...
Page 74: ...66...
Page 75: ...67...
Page 76: ...68...
Page 77: ...69...
Page 78: ...70...
Page 80: ......