Fig. 26 Control panel electronic modulating version (version EM)
7
OPERATION AND FAULT INDICATION
7.1
Function
The water heater starts up in the sequence described below:
7.2
Regulation
The burner (input) is controlled through a butterfly valve and
7.3
Control panel
To assist with fault finding the control panels incorporate a
Heat demand. Ignition of pilot flame. As soon as pilot flame is
detected, an ionisation current will pass to the flame safeguard
control box. The main gas valve opens and gas ignites over
complete burner tray. Main burner flame is detected by a sens-
ing electrode. The modulating control will commence from low
fire condition.
modulates between 20 % and 100 % heat demand. If the heat
demand is smaller than 20 %, the burner will remain off. The
temperature is controlled through or an electronic PID regulator
(EM-version).
number of warning indicators and switches.
1
Power on/off switched indicator
2
Water heater lock-out indicator (central alarm and/or ionisation
lock-out)
3
Reset switch
4
Overheat temperature indicator (off when water heater over-
heated)
5
Insufficient water flow indicator
6
Low gas pressure indicator
(optional)
7
Gas leak indicator
(optional)
8
High gas pressure indicator
(optional)
9
By pass switch for high limit test
10
Hours run indicator (EM only)
T Temperature
Gauge
P
Pressure Gauge