Order number: 900211.002
Page 5
First control level:
Adjusting the operating time
By pressing th SET-key the operating time t1 is indicated.
By additionally pressing the UP- or DOWN-key the time can be set.
Para-
meter
Function
Adjustable range
Standard
setting
Customer
setting
t1
Operating time (setpoint) K1
see P1
1:11 hrs
Second control level (P-parameter):
Adjusting of timer parameters
Simultaneously pressing the UP and DOWN key for at least 4 seconds opens an intermediate menu with
“PA0” in the display.
If there is no password specified for access to the actual parameter list (= factory setting), a short press of
the SET key opens the timer parameters, starting with P1
With the UP and DOWN keys the list can be scrolled in both directions.
Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or DOWN
key at the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by simultane-
ously pressing the UP and DOWN key for approx. 4 seconds
Para-
meter
Function
Adjustable range
Standard
setting
Customer
setting
P1
Operating range t1 (K1)
0: 0...99.9 sec.
1: 0...99 min. 59 sec.
2: 0...99 Std. 59 min.
2
P2
Operating range TA1, TA2
0: 99.9 sec.
1: 99 min. 59 sec.
0
P3
Derivative time TA1
0... see P2
0 sec.
P4
Derivative time TA2
0... see P2
0 sec.
P5
Function input E1 (START)
0: start with closed contact
1: start with opened contact
0
P6
Function input E2 (STOP)
0: stop with closed contact
1: stop with opened contact
0
P7
Function output K1
0: activated during timer
1: deactivated during timer
0
P8
Function output K2
0: activated during timer
1: deactivated during timer
0
P9
Buzzer function K2
(after t1+TA2 or after P15, see P13)
OFF: no buzzer
1: continuous
2: intermittent
1
P10
Trigger start function
0: key or switching input
1: only key
1: only switching input
0
P11
Trigger stop function
0: key or switching input
1: only key
1: only switching input
0
P12
Display mode operating time t1
0: countdown
1: elapsed time
0
P13
Stop of K2
(no timer P15 for K2 if P13=0 or
P13=1)
0: with STOP
1: with STOP or START
2: P15 starts after t1+TA2, no restart
3: P15 starts after t1+TA2, restart
0