Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A50
Minimum action time
contact K1 ”On”
0…600 sec.
0 sec.
A51
Minimum action time
contact K1 ”Off”
0…600 sec.
0 sec.
A54
Delay after “Power-on”
0…600 sec.
0 sec.
A56
Alarm suppression after
"Power-On"
0…60 min.
0 min.
A60
Sensor type
11: Pt100 2-wire
21: PTC
22: Pt1000 2-wire
11
A70
Software filter
1:
inactive
2…32: average value with 2…32
measuring values
4
A80
Temperature scale and display
when in Standby-Mode
0: Fahrenheit (“AUS”)
1: Celsius (“AUS”)
2: Fahrenheit (“OFF”)
3: Celsius (“OFF”)
1
A85
Function key A
(if available)
0: no function
1: indicate actual value (if A32=1)
2: activate setpoint S1‘ (if A33>0)
0
A86
Function key B
(if available)
0: no function
1: indicate actual value (if A32=1)
2: activate setpoint S1‘ (if A33>0)
0
A87
Function standby key
0: no function
1: controller On/Off (Standby), same
condition after connecting mains
2: like 1, always off after connecting
mains
3: like 1, always on after connecting
mains
1
A88
Delay for standby ON
0.1 ... 3.0 sec.
0.1 sec.
A89
Delay for standby OFF
0.1 ... 3.0 sec.
0.1 sec.
Pro
Program version
-
-