background image

 

 

Parameter description: 
 

The following values can change the equipment characteristics 

and are therefore to be set with utmost care. 

 
 

A1: Switch mode contact K1 

The switch mode for the relay, i.e. cooling or heating function, can be programmed independently 
at works. Heating function means that the contact opens as soon as the setpoint is reached, thus 
power interruption. At cooling function the contact closes, if the actual value is above the required 
setpoint. (see fig. 1 + 2) 
 

A3: Function of contact K1 at sensor error 

At sensor error the relay falls back into the condition pre-set here. If there is a data-loss in 
parameter memory (display indicates “EP”) both contacts K1 and K2 are switched off. 
 

A8: Display mode 

The value can be indicated in integrals or with decimals in 0.5°K or 0.1°K. At indication in 0.5°K the 
value is rounded up or down. In general, all parameter indications are presented in 0.1°K. 
 

A19: Parameter lock 

This parameter enables locking of each parameter level. If third level is locked, only parameter A19 
may be changed. 
 

A30: Function alarm exit 

The alarm exit evaluates an upper and a lower limit value (see parameters P30 and P31), whereas 
a selection is possible as to whether the alarm is active if the temperature lies within these two 
limits, or whether the alarm is released if the temperature lies beyond them. In the case of sensor 
error, the alarm is activated independently of this adjustment (see fig. 3 – 4 at parameters P30/31). 
 

A31: Special function at boundary or range alarm 

Here can be selected whether, in the case of an alarm, the indication to flash and/or the buzzer is 
to start. Sensor alarm (display F1L or F1H) is indicated independently thereof by flashing display 
and the buzzer. 
 

A32: Setpoint display 

A32=0 indicates the actual value, A32=1 statically indicates the setpoint S1 or S1’ in the display. 
Therefore, the current actual value can only be indicated with parameter P0. 
 

A33: Adjustment of setpoint S1‘ (not available on all types of controllers) 

By closing switching input E1, setpoint S1 can be switched to a setpoint S1’. Setpoint S1’ can be 
either relative to setpoint S1 or an independent, freely adjustable, control setting.  
The setpoint S1’ can only be accessed if input E1 is closed. The setpoint S1’ can only be activated, 
if the external input is configured for setpoint change-over (parameter A81=2). 
 

A40: Hysteresis mode contact K1 

These parameters allow selection as to whether the hysteresis value which is adjustable with P32, 
is set symmetrically or one-sided at the respective switching point. At symmetrical hysteresis, half 
of the hysteresis’ value is effective below and half of the value above the switching point. The one-
sided hysteresis works downward with heating contact and upward with cooling contact (see fig. 1 
+ 2).  
 

Summary of Contents for 900321.003

Page 1: ...binet It was specifically developed for direct switching at high per formances Given the high maximum electric load of 16A ohm and 6A inductive it can operate without cut out relay in many cases The c...

Page 2: ......

Page 3: ...essed the display indicates the actual value of the temperature Pressing the SET key the setpoint shows on the display If the setpoint is to be changed the SET key is to be kept pressed while adjustin...

Page 4: ...o key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P0 Actual measuring value P2 Hysteresis contact K1 0 1 99 9 K 1 0 K P4 Control range li...

Page 5: ...ances or extremely long sensor lines The regulation measure value is increased or decreased by the here adjusted value P19 Key lock The key lock allows blocking of the control keys In locked condition...

Page 6: ...mperature value is reached The defrosting time set with d3 nevertheless runs at the same time i e it functions as safety net to terminate the defrosting process in case the defrosting temperature is n...

Page 7: ...t 1 cooling contact 2 function alarm K1 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A8 Display mode all parameter indications are presented in 0 1 K 0 integrals 1 decimals in...

Page 8: ...re scale and display when in Standby Mode 0 Fahrenheit AUS 1 Celsius AUS 2 Fahrenheit OFF 3 Celsius OFF 1 A85 Function key A if available 0 no function 1 indicate actual value if A32 1 2 activate setp...

Page 9: ...m is released if the temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment see fig 3 4 at parameters P30 31 A31 Special function at boundary...

Page 10: ...ameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal process A8...

Page 11: ...lock active Change parameter P19 or A19 display flashes Temperature alarm at too high or too low temperature if activated see A31 Buzzer Temperature alarm at too high or too low temperature if activa...

Page 12: ...conductive strips Display One 3 digit LED Display height 13 mm colour red 1 LED diameter 3mm colour red for status display of K1 Power supply 230V 50 60 Hz power consumption max 5 VA Connectors screw...

Reviews: