Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
A31
Special function at boundary or
range alarm
0: no special function
1: flashing display
2: buzzer
3: flashing display and buzzer
4: like 3, buzzer can be cancelled
5: like 4, cancelled buzzer restarts
after 10 min.
6: like 4, cancelled buzzer restarts
after 30 min
0
A32
Setpoint display
0: display shows actual value
1: display shows setpoint S1 (S1‘)
0
A33
Type of setpoint S1‘
0: not activated
1: relative to setpoint S1
2: absolute (freely adjustable)
1
A40
Hysteresis mode contact K1
0: symmetrically
1: one-sided
1
A41
Hysteresis mode contact K2
0: symmetrically
1: one-sided
1
A50
Minimum action time
contact K1 ”On”
0…600 sec.
0 sec.
A51
Minimum action time
contact K1 ”Off”
0…600 sec.
0 sec.
A52
Minimum action time
contact K2 ”On”
0…600 sec.
0 sec.
A53
Minimum action time
contact K2 ”Off”
0…600 sec.
0 sec.
A54
Delay after “Power-on”
0…600 sec.
0 sec.
A55
Mutual delay of contacts
K1 and K2
0...600 sec.
0 sec.
A56
Alarm suppression after
"Power-On"
0…60 min.
0 min.
A60
Sensor type
11: PT100 two-wire
12: PT100 three-wire
21: PTC
22: PT1000 two-wire
23: PT1000 three-wire
31: voltage input 2-10V
or current input 4-20mA
32: voltage input 0-10V
or current input 0-20mA
21
A70
Software filter
1:
inactive
average value with:
2: 2 measuring values (ca. 0.6s)
4: 4 measuring values (ca. 1.2s)
8: 8 measuring values (ca. 2.4s)
16: 16 measuring values (ca. 4.8s)
32: 32 measuring values (ca. 9.6s)
64: 64 measuring values (ca. 19.2s)
128: 128 measuring values
(ca. 38.4s)
8