background image

StormPro

® 

2100DC

Heavy Duty 12V DC Pump

OPERATION MANUAL

Dated: 03/15/2013

Document Name: StormPro_2100DC_OM

Page 4 of 8

Register your product at www.sumpro.com

1.  Take the negative (-) black battery wire and 

fasten the ring terminal securely to  the negative 

(-) battery post on top of the battery.

2.  Take the Po) red battery wire and fasten 

the ring terminal securely to the Po) 

battery post on top of the battery. 

3. 

The  battery  terminals  are  different  sizes  to 

ensure correct polarity, do not force  the 

terminal on to the plug if it does not fit. Connect 

the  negative (-) black wire to the charger units 

(-) battery post and connect the positive (+) red 

wire to the charger units positive (+) battery 

post. 

4.  After all the terminals have been installed 

properly plug the charger unit into a dedicated 

115V wall outlet.

Error Description

Possible Causes

Fix

The battery failed

pre-qualification test

The battery is highly sulfated

The charger is connected to a six-volt battery

Replace the battery with a 12-volt deep-cycle marine battery

Replace the battery with a 12-volt deep-cycle marine battery

Battery over-voltage

The charger is connected to a 24 volt battery

Replace the battery with a 12-volt deep-cycle marine battery

Charge time monitor

Battery took too long to complete its charge:

A. Load applied (e.g. the pump motor   

    started) during charging

B. The battery ampere-hour rating is too

    large (max. 130 ampere-hours)

A: Be sure the pump cannot start during  

     charging; reset the charger

B: Replace with correct size battery

Excessive battery 

drain

Pump motor ran during charging (that is, with the 

main A.C. power ON), causing the system to shut 

down

Check primary sump pump. The BBU generally runs only 

when the main A.C. power is out. If there has not been any 

power outage and the BBU has run, the primary pump itself 

may have failed

Reverse battery 

connection

Charger is connected backwards to the battery. 

(That is, charger (+) to battery (-) and vice versa)

Reconnect charger (+) to battery (-)/(-) to (-)

Battery overheated

Cells in an old battery may deteriorate with age

Replace the battery with a 12-volt deep-cycle marine battery

Charging error

An internal error occurred in the charger during one 

of the charging states

Unplug the charger for 10 seconds and then plug it in again. 

If error occurs again, refer to table below

Summary of Contents for 2100DC

Page 1: ...re will come in contact with splash on or drip on unit Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause electric shock and or a fire hazard WARNING Risk of electrical shock In the event of a short circuit grounding reduces the risk of shock by providing an escape wire for the electrical current The StormPro 2100DC must be properly grounded The St...

Page 2: ... a dilute sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosive The following procedures should be observed 1 Wear full eye protection and clothing Battery Precautions 2 If electrolyte contacts the skin wash it off immediately 3 If electrolyte contacts the eyes flush thoroughly and immediately with water Seek medical attention 4 Spilled electrolyte should b...

Page 3: ...e sure that the charger unit is not plugged into the wall outlet before connecting the terminals The backup pump backup float switch and battery will all connect into the back of the charger unit Make sure to use correct polarity Pump Start with the backup pump wires the terminals are different sizes to ensure correct polarity do not force Float Switch Installation Charger Unit Installation Tools ...

Page 4: ...y with a 12 volt deep cycle marine battery Battery over voltage The charger is connected to a 24 volt battery Replace the battery with a 12 volt deep cycle marine battery Charge time monitor Battery took too long to complete its charge A Load applied e g the pump motor started during charging B The battery ampere hour rating is too large max 130 ampere hours A Be sure the pump cannot start during ...

Page 5: ...een Flashing Yellow Green Battery Overheated Charge Time Monitor Excessive Battery Drain Failed Pre Qualification Test Battery Over Voltage Reverse Battery Connection Output Over Current Charger Light On Off Flashing Alarm Buzzer Indicates All LEDs Flash ONCE Off Connected system to AC power or to battery or pressed Reset when in ERROR mode AC Power Status On Very Slow Flash Off Off System is rece...

Page 6: ...ump run time left Alarm CANNOT be silenced On Beeping Fast beep in synch with one or more of the AC Power Status Pump Run Status or Alarm Silence LEDs and with the Charger Mode LED flashing alternately YELLOW GREEN System is in ERROR mode Refer to ERROR Mode Charts On Beeping Fast beep in synch with Pump Run Status LED Pump is running None Alarm will stop when pump stops running To silence alarm p...

Page 7: ...StormPro 2100DC Heavy Duty 12V DC Pump OPERATION MANUAL Dated 03 15 2013 Document Name StormPro_2100DC_OM Page 7 of 8 Register your product at www sumpro com Notes ...

Page 8: ...an to correct a defect in a product shall extend the Warranty beyond the period set forth above Metropolitan shall not be obligated to remedy any defect where otherwise required pursuant to the Warranty unless and until Buyer notifies Metropolitan in writing of the defect and then only if such notification is made prior to the expiration of the period set forth above 3 Process of Claims and Repairs ...