ASSEMBLY INSTRUCTIONS FOR:
Page 10
11/07/00
To fit flue gas collector hood to rear section
The flue gas housing is fitted on ex works, but not sealed in
place.
Fitting the flue gas collector hood
Dismantle flue gas collector hood (1)
Cover joint of the rear section and flue gas collector hood with
boiler mastic sealing strand
Push flue gas collector hood over set screws at rear section.
Fit spacing bracket for side jacket (3) on right and left hand sides.
Tighten nuts in a diagonal fashion.
Fitting the firing chamber rear wall protective refractory.
1. Open
burner
door
2. Place protective rear wall refractory as shown, per diagram.
The refractory is not fixed into position, it simply leans
against the section wall.
To convert the burner door from right hand side to left hand
side opening
1. Firmly shut the burner door
2. Undo and remove Hexagonal screws (18) on the lower left
locking plate (17)
3. Undo and remove stud bar (19) on front section
4. Undo and remove split pin (20) and crown nut (21) at the top
right hand side
5. Undo hexagonal screws (18) on the hinge side, convert the
entire hinge with stud bar (22) and fit on the opposite side on
the bottom
6. Fasten converted stud bar (19) on the opposite at the front
section, firmly draw locking plate (17) concentrically to screw
bar (19) using hexagonal screw (18)
7. The other diagonals as described in points 1-6
Flue-gas collector hood assembly
Fitting rear wall protective refractory.
Hinge and burner door assembly.
ASSEMBLY
INSTRUCTIONS
FOR:
RU 1s Assembly