K4
Changes in models reserved.
Dimensions not binding!
Operation
Burner Ignition
In case of valid heat demand request, ignition sequence will be started. In case of failed ignition,
controller will try to reignite for a defined number of times. At the first ignition trial, the burner will
ignite with fan speed set by Ignition fan speed value. As soon as the flame presence is validated, fan
speed moves according to the heat demand type. If no successful ignition after programmed number
of retrials, flame lockout error will be indicated.
CH Mode
Operation in the CH mode is possible only when Winter is enabled.
CH heat demand can be generated by Room Thermostat SELV input or by OpenTherm control unit. If
remote control is connected and communication is validated, room thermostat input is ignored.
ON/OFF control (no OTC – no OpenTherm room unit)
Closure of Room Thermostat contact generates an heat demand in CH mode.
Supply pump is switched on.
Flame indication is showing:
HD + Flame ON + power < 30%
HD + Flame ON + power > 30% <75%
HD + Flame ON + power > 75%
If a higher priority operating demand is received, the function in progress is stopped to meet this
demand.
ON/OFF control (OTC – no OpenTherm room unit)
Outdoor temperature sensor must be connected to the controller.
User
21
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
20,0
15,0
10,0
5,0
0
-5,0
-10,0
-15,0
-20,0
Ž
ád
an
á
te
pl
ot
a
to
pn
é
vo
dy
°C[
]
křivka 4
křivka 8
křivka 12
křivka 16
křivka 20
křivka 25
křivka 30
Outside temperature [°С]
Fig. №. 9
By pressing
i
K3
pushbutton twice, it is possible to see following information:
1time PT1000 temperature (solar sensor temperature), if sensor is not connected, LCD shows ---
2time OTC temperature, if sensor is not connected, LCD shows ---
Value stays on the LCD for 5 sec. (after releasing
i
K3
push button):
Frost protection
Frost protection is enabled in all the specified operating modes.
Legionella protection
The design of the boiler tank is activated protection against legionella.
Supply over temperature on DHW mode
This functionality is valid for all of 5 DHW mode configurations.
During a DHW heat demand, the temperature value read by the supply sensor is continuously monitored.
5.3
Lockout condition codes
Lockout condition is given with the capital "
E
" (error) on the status display and error code on the temperature display:
Symbols
or
are being shown only in case of lockout condition which needs to be solved by Service people.
Error code
Description
E01
Ignition Lockout indication
E02
False flame indication
E03
High limit temperature protection (supply or return sensor)
E05
No frequency feedback from fan after 1 minute
E08
Flame circuit failure
E09
Valve feedback error
E12
EEPROM integrity lockout
E15
Drift sensors check failed
E16
Supply sensor stuck_at test failed
E17
Return sensor stuck_at test failed
E18
Cracked sensor test failed
E21
Adc failure
E33
Return water temperature sensor error
E35
Supply water temperature sensor error
E82
Flame loss
C
H
s
et
poi
nt
[°
С
]
OTC curve 30
OTC curve 25
OTC curve 20
OTC curve 16
OTC curve 12
OTC curve 8
OTC curve 4
26