K4
Changes in models reserved.
Dimensions not binding!
Operation
By pressing pushbutton twice, it is possible to see following information:
First time – PT1000 temperature (solar sensor temperature), if sensor is not connected, LCD shows ---
Second time – OTC temperature, if sensor is not connected, LCD shows ---
Value stays on the LCD for 5 sec. (after releasing
i
K3
push button):
Frost protection
Frost protection is enabled in all the specified operating modes.
Legionella protection
The design of the boiler tank is activated protection against legionella.
Supply over temperature on DHW mode
This functionality is valid for all of 5 DHW mode configurations.
During a DHW heat demand, the temperature value read by the supply sensor is continuously moni-
tored.
6.3 Lockout Condition Codes
Lockout condition is given with the capital „E“ (error) on the status display and error code on the
temperature display:
Symbols
or
are being shown only in case of lockout condition which needs to be solved by
Service people.
Error code Description
E01
Ignition Lockout indication
E02
False flame indication
E03
High limit temperature protection (supply or return sensor)
E05
No frequency feedback from fan after 1 minute
E08
Flame circuit failure
E09
Valve feedback error
E12
EEPROM integrity lockout
E15
Drift sensors check failed
E16
Supply sensor stuck_at test failed
E17
Return sensor stuck_at test failed
E18
Cracked sensor test failed
E21
Adc failure
E33
Return water temperature sensor error
E35
Supply water temperature sensor error
E82
Flame loss
27