K4
Changes in models reserved.
Dimensions not binding!
Operation
E01
Lockout signal after the ‚no flame‘ and all ignition trials are expired.
This error stops the boiler. To return to normal operation again, manual/remote reset is required.
E02
If the flame signal is measured with no current heat demand, error 2 is displayed.
This error stops the boiler. To return to normal operation again, manual/remote reset is required.
E03
High limit temperature protection detected on flow or return temperature sensor.
This error stops the boiler. To return to normal operation again, manual/remote reset is required.
E05
Fan driving problem – if the controller doesn’t detect the expected tacho signal from the fan for an additional
minute, this error will be set.
This error stops the boiler. To return to normal operation again, manual/remote reset is required.
E08
Flame circuit failure – The detected flame level is outside expected bounds, pointing to a problem with the
electronic components.
E09
Feedback error – the valve feedback doesn’t respond to controller commands.
E12
The EEPROM check fails. The data in EEPROM are corrupted.
E15
Drift sensors check failed. Manual/remote reset is required.
E16
Stuck_at test on Flow sensor failed. Manual/remote reset is required.
E17
Stuck_at test on Return sensor failed. Manual/remote reset is required.
E18
Crack sensor test failed. Manual/remote reset is required.
E21
Adc failure. The adc test executed at runtime fail, that detect a major fault on electronic components.
E33
Return sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes exceeds the range
(00÷125°C), this error will be displayed. In case sensor is back to normal operating range, the lockout can be
cleared by manual/remote reset. In error mode, heat demands will be disabled. In case two or more sensors are
broken, the controller will pick up the first one that was outside of operating range. Resolving this situation can
only be achieved if the sensor is within operating range again. The lockout error on this sensor is necessary be-
cause is it used for high limit protection.
E35
Flow sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outdoor the range
(00÷125°C), this error will be displayed. In case sensor is back to normal operating range, the lockout can be
cleared by manual/remote reset. In error mode, heat demands will be disabled. In case two or more sensors are
broken, the controller will pick up the first one that was outside of operating range. Resolving this situation can
only be achieved if the sensor is within operating range again. The lockout error on this sensor is necessary be-
cause is it used for high limit protection.
E82
Flame loss. The loss of flame during actual HD is counted and if it reaches a defined number of losses (#3) this
error is set. This error stops the boiler. To return to normal operation again, manual/remote reset is required.
The counter is cleared if the flame is not lost for a defined time (4 minutes) or the HD is removed.
28