Commissioning
Param. Name
Range
Unit
Setting (Nat. Gas models)
Setting (Propane models)
K4G1..
K4G2..
K4G3..
K4G1..
K4G2..
K4G3..
P00
DHW configuration
1=Instantaneous
num.
5
1
3
5
1
3
2=Instant Solar
3=Storage tank
4=Solar storage tank
5=CH only
P01
Gas type
0=Natural
num.
0
0
0
1
1
1
1=LPG
P02
Ignition fan speed
150–635
RPM x 10
400
400
400
400
400
400
P03
Water filling
0=Enable
num
0
0
0
0
0
0
1=Disable
2=Auto
P04
DHW user set point max.
30–65
°C
x
65
65
x
65
65
P05
DHW max. fan speed
150–635
RPM x 10
x
635
635
x
635
635
P06
DHW min. fan speed
150–635
RPM x 10
x
150
150
x
150
150
P07
DHW pump overrun time
0–255
min.
x
1
1
x
1
1
P08
DHW frost protection ON
0–50
°C
x
8
8
x
8
8
P09
DHW frost protection OFF
0–50
°C
x
35
35
x
35
35
P10
DHW heat demand type
0=sensor
num.
x
x
0
x
0
x
1=thermostat
P11
Antilegionella set point
0–70
°C
x
x
70
x
70
x
P12
Antilegionella timeout
1–7
day
x
x
7
x
x
7
P13
Supply temp. delta
0–20
°C
x
x
5
x
x
5
P14
Max. supply temp.
0–90
°C
x
x
85
x
x
85
P15
Solar enable temp.
5–20
°C
x
x
x
x
x
x
P16
Solar disable temperature
5–20
°C
x
x
x
x
x
x
P17
Solar pump min. running
time
0–120
sec.
x
x
x
x
x
x
P18
Solar limit temperature
100–150
°C
x
x
x
x
x
x
P19
Solar storage tank limit
temperature
50–100
°C
x
x
x
x
x
x
P20
Solar mode functionality
0=solar priority
num.
x
x
x
x
x
x
1=parallel
P21
Heat demand delay after
Solar pump activation
0–60
sec.
x
x
x
x
x
x
P22
Delta for virtual DHW user
set point
0–30
°C
x
x
x
x
x
x
P23
CH user set point maximum 20–90
°C
80
80
80
80
80
80
P24
CH maximum fan speed
150–635
rpm x 10
635
635
635
635
635
635
P25
CH minimum fan speed
150–635
rpm x 10
150
150
150
150
150
150
P26
CH OFF time
0–10
min.
1
1
1
1
1
1
P27
CH pump overrun timer
0–255
min.
3
3
3
3
3
3
P28
CH pump
0= Continuous
num
0
0
0
0
0
0
1=Overrun
P29
CH minimum time
0–5
min.
1
1
1
1
1
1
P30
CH slope rate
0–60
°C/min.
4
4
4
4
4
4
P31
CH frost protection ON
0–10
°C
5
5
5
5
5
5
P32
CH frost protection OFF
0–10
°C
10
10
10
10
10
10
P33
OTC curve selection
0–30
num.
0
0
0
0
0
0
P34
Supply for CH thermostatic
pump overrun OFF
0–100
°C
80
80
80
80
80
80
P35
Supply for CH thermostatic
pump overrun ON
0–100
°C
85
85
85
85
85
85
P36
System configuration
Bit x: cleared/set
num.
4
4
4
4
4
4
Bit 2: WP switch/sensor
P37
DHW request type
0=Fugas Flow sensor
num.
x
3
x
x
3
x
1=Bitron Flow sensor
2=Kramer Flow sensor
3=Flow switch
2=Honeywell Flow sensor
K4GXH33X - Honeywell electronics parameters set in the factory
(service parameters list neXsys S4962V3224)
Servicing
50
13
Servicing Inspection of the Boiler
The user is obliged ensure regular annual servicing inspections of the boiler.
When these conditions are not observed the owner cannot clam warranty repairs.
The instructions for the servicing inspection procedure is available for servicing organizations.
Main points of the inspection:
•
Check of liquids leakage from boiler's joints;
•
Check of pressure in the expansion tank;
•
Check of the adjustment of CO
2
of the gas valve (emission), should be performed 1 x per year;
•
Disassembling of the burner and check of exchanger and electrodes state;
•
Check of siphon clogging for condensate discharge;
•
Bleeding of the exchanger;
•
Check of chimney flue.
Attention: Before you remove the boiler casing, disconnect the boiler from the electric supply.
Fig. №. 32
Exchanger inspection