TECHNICIAN MENU
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
3. SYSTEM SETTINGS
C
1.Boiler parameters
C
1.Ignition power
C
36%
0-100%
D
B
D
2.Delay siphon check
C
10s
0-60s
D
3.Number of boiler pump
C
Two pumps
Pump and
3-way valve /
Double pump
D
4.Pump speed max
C
100%
15-100%
D
5.Pump speed min
C
30%
15-100%
D
6.Anti-Legionella
C
Disabled
Enabled/
disabled
D
7. Heat exchanger protection
C
Enabled
Enabled/
disabled
D
8. Heat exchanger delta
C
10°C
5-20°C
D
9.Modbus parameters
C
0
0-255
D
10. 3-way valve travel time
C
10s
1-255s
D
2. User interface settings
C
1.Language
C
Italiano
English /
Italiano
D
2. Select Units
C
Celsius
Fahrenheit /
Celsius
D
3. Set date
C
Enter the date
D
4.Set time
C
24 hours
24 hours /
12 hours
D
3.Maintenance settings
C
1.Service information
C
Enter tel. n°
D
2.Service due date
C
Enter date
4. DIAGNOSTICS
C
1.Boiler information
C
--->
--->
--------
D
B
D
2.Lockout history
C
--->
--->
--------
D
3.Manual Test
C
--->
--->
OFF
OFF / 0-100%
- 36
-