The setting of the “gas change” parameter AUTOMATICALLY sets the blower RPM as stated in the table.
DESCRIPTION
S - AF
115
150
200
240
280
Nominal heating output - Min - Max
21.0 - 113.0 30.0 - 150.0 35.5 - 200.0 42.5 - 235.0 49.5 - 275.0
kW
Operating RPM
a G20
1665 - 7400 1650 - 6250 1230 - 5600 1320 - 5800 1300 - 5800
rpm
Frequency
55.5 - 246.7 55 - 208.3
61.5 - 280
66 - 290
65 - 290
Hz
Operating RPM
a G31
1665 - 7400 1650 - 6250 1230 - 5600 1320 - 5800 1300 - 5800
rpm
Frequency
55.5 - 246.7 55 - 208.3
61.5 - 280
66 - 290
65 - 290
Hz
HEATING UNIT IGNITION
To start up the heating unit:
- Ensure that a jumper is wired in or that an on-demand room
thermostat is set between terminals 7 and 8. The heating unit will
not work without these conditions.
MANUAL TEST function
This procedure enables the user to override a heating cycle, with
settable power, for a maximum duration of 15 minutes
7
8
7
8
Room
Thermostat
230Vac
43 44
43 44
Room
Thermostat
24Vac
Key to
press
Description
Display
F
A
to display the MENU screens
to enter the TECHNICIAN menu, which requires
entry of the PASSWORD
date
OUTSIDE
7
o
C
69
o
0.0
OFF OFF
time
MENU
USER
TECHNICIAN
A
a
A
Key to
press
Description
Display
D
C
to select the output corresponding to the appliance
model
to confirm the selection and return to the INITIAL
screen.
G31
1. 115kW
2. 150kW
3. 200kW
4. 240kW
5. 280kW
to confirm
oK
Restore factory data
PLEASE WAIT
to confirm
oK
- 47
-
INST