S-CB
+
Boiler Range Manual
87
11.4 Cascade control
The following information is also found in the specific cascade manual, supplied standardly with Strebel
cascade accessories or on request.
Before commissioning a cascade installation, a number of parameters have to be changed.
These parameters can be programmed on the unit itself, without the use of a computer.
Changes in parameter may only be carried out by a skilled commissioning/service engineer, who has had
specific training for setting up the Ambassador
+
range boilers. He will be able to check whether the instal-
lation functions correctly after the parameter change has been done.
For programming
all parameters
of the boilers one needs to have a laptop with the appropriate EHS software and
an interface cable for connecting the laptop to the boiler control (one order no.: S04.016.586). This software is used
for programming but also shows all measured temperatures and cascade behaviour during operation and ser-
vice/fault history.
11.4.1
P
ARAMETER SETTINGS FOR CASCADED BOILERS
Before programming the cascaded boilers, make sure that all boilers are connected (wire) with each other. Use
connection 17 and 18 of each boiler.
Remind
: do not alternate these connections, so always connect 17 to 17 and 18 to 18.
After connection every boiler must be programmed. This can be done at the control panel. Press the [MENU] but-
ton and select the [PARAMETER] menu. See graphics below.
Operating screen:
H E A T I N G : S T A N D - B Y
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Press [MENU]
Main menu screen:
M a i n M e n u
S e t p o i n t s
Select "Parameter" using [◄] & [►] and press [ENTER]
After this, use the password
for installer’s level 2.
Parameter menu:
I n s t a l l e r
c o d e
0 0 0 0
Enter the 4-digit
code with the [◄] & [►] and the
[▲] & [▼] buttons and select [ENTER]
The code will blink a few seconds and when entered
correctly, the following parameters will be displayed.