10
Boiler Model
S-CBX 85 S-CBX 105 S-CBX 125 S-CBX 155
EMISSION
Values min-max:
CO
2
flue gas
3
G20
%
7.9 – 8.4
7.9 – 8.4
7.9 – 8.4
7.9 – 8.4
G25.3
%
8.4 – 8.2
8.4 – 8.2
8.4 – 8.2
8.4 – 8.2
G31
%
10 - 10
10 - 10
10 - 10
10 - 10
O
2
flue gas
3
G20
%
6.9 - 6.0
6.9 - 6.0
6.9 - 6.0
6.9 - 6.0
G25.3
%
5.7 - 6.1
5.7 - 6.1
5.7 - 6.1
5.7 - 6.1
G31
%
5.7 - 5.7
5.7 - 5.7
5.7 - 5.7
5.7 - 5.7
NOx class
-
6
6
6
6
Flue gas temperature at combustion air
temperature = 20 °C
°C
60 - 90
Mass flow flue gas (min/max)
g/s
8.0 - 42
10 - 51
12 - 62
15 - 76
Available pressure for the flue system
4
Pa
200
INSTALLATION
Resistance boiler
T = 20 K m.W.C
4.0
3.4
3.8
3.6
T = 25 K m.W.C
2.8
2.3
2.5
2.4
Pressure boiler min-max.
bar
1.0 – 6.0
Max. flow temperature
°C
90
ELECTRIC
Maximum power consumption
5
W
190
280
280
280
Power supply
V/Hz
230 / 50
Protection class
-
IPX4D
NOTES
3
CO
2
of the unit measured/set without the boiler front panel in place
4
Maximum allowed combined resistance of flue gas and air supply piping at high fire
5
Power consumption is measured without circulation pump