31
A few examples of flue gas material suitable for the S-CBX boilers:
CE String for Plastic PPs: EN14471 T120 P1 W 2 O(30) I C/E L
CE String for Stainless Steel: EN1856-1 T250 P1 W V2-L50040 O (50)
When selecting flue gas systems, be aware that the minimum requirements are met. So only select flue gas
materials having the same or better properties than this table.
Never use aluminium containing flue gas pipes in these boilers.
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other
appliance.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.
Connecting diameters and tolerances:
mat
boiler
d
nom
[mm]
D
outside
[mm]
d
inside
[mm]
L
insert
[mm]
SS
S-CBX 85, 105, 125
100
100 +0,3/ -0,7
101 +0,3/ -0,3
50 +2/ -2
SS
S-CBX 155
150
150 +0,3/ -0,7
151 +0,5/ -0,5
50 +2/ -2
PP
S-CBX 85, 105, 125
100
100 +0,6/ -0,6
50 +20/ -2
PP
S-CBX 155
150
150 +0,9/ -0,9
50 +20/ -2
Multiple boilers can be connected to a common duct. These flue gas systems for multiple boiler installations must
always be engineered as zero or negative pressure systems; this to prevent the risk of recirculation of the flue
gases. Consult the flue gas supplier for detailed information and engineering. See also the cascade chapter for
these multiple boiler installations.
READ THE MANUAL PROVIDED BY THE VENT GAS AND AIR SYSTEM SUPPLIER
CAREFULLY
9.2 Polypropylene
This product has been approved for use with polypropylene vent with the manufacturers listed.
All terminations must comply with listed options in this manual and be a single-wall vent offering.
For support and special connections required, see the manufacturer's instructions.
All vent is to conform to standard diameter and equivalent length requirements established.
9.2.1
F
LEXIBLE POLYPROPYLENE
For use of flex pipe, it is recommended to have the vent material in 0 °C (32°F) or higher ambient space before
bending at installation. No bends should be made to greater than 45° and ONLY installed in vertical or near vertical
installations.
9.3 Stainless steel vent.
This product has been approved for use with stainless steel using the manufacturers listed.
Use only the materials and vent systems listed.
DO NOT mix vent systems of different types or manufacturers. Failure to comply could result
in severe personal injury, death, or substantial property damage.
Installations must comply with applicable national, state, and local codes.
Installation of a stainless-steel vent system should adhere to the stainless-steel vent
manufacturer’s installation instructions supplied with the vent system.
NOTICE
WARNING
NOTICE
Summary of Contents for S-CBX 105
Page 2: ......
Page 40: ...40 9 10 Flue Terminal Positioning ...
Page 42: ...42 9 11 1 FIGURE 12 LINE G ...
Page 55: ...55 11 5 Ladder Logic Diagram ...
Page 56: ...56 11 6 Electrical schematics ...
Page 57: ...57 ...
Page 137: ......