66
12.5.3 A
PPLIANCE SELECTION
The control is designed to store specific parameter sets of different boiler models.
By defining specific setting for different appliance models the same control can be used for a complete product
range. Depending on which model boiler the control is applied to, it only will be necessary to change just one single
parameter. See chapter 18.4: "Change the appliance type" for details.
When this parameter is changed the following settings are changed:
• Maximal fan speed
• Minimal fan speed
• Ignition speed*
• Maximum flue gas temperature
*Ignition speed is the same as Pre-Purge Speed and Post Purge speed.
The following appliances are available:
PCB 1 – S-CBX 85 & 105
Appliance type 50 – S-CBX 85 on Natural Gas.
Appliance type 51 – S-CBX 85 on LPG.
Appliance type 52 – S-CBX 105 on Natural Gas.
Appliance type 53 – S-CBX 105 on LPG.
Appliance type 54 - Not Used
Appliance type 55 - Not Used
PCB 2 – S-CBX 125 & 155
Appliance type 50 – S-CBX 125 on Natural Gas.
Appliance type 51 – S-CBX 125 on LPG.
Appliance type 52 – S-CBX 155 on Natural Gas.
Appliance type 53 – S-CBX 155 on LPG.
Appliance type 54 - Not Used
Appliance type 55 - Not Used
12.6 Ignition cycle
During the ignition cycle multiple safety checks are active
False flame detection
If flame is detected at the end of the pre-spark period (
Pre-ignite
) a lockout error occurs
Re-ignition
If at the end of the safety period, no flame is detected the control will go to post-
purge to remove the unburned gas. After this a re-ignition attempt is started
following the same cycle.
The number of re-ignition attempts is limited to
Max_Ignit_Trials
after which a lockout
occurs.
Flame establishing time
Sparking stops in the
Flame Proving
state to allow for ionization
detection. The
Flame Proving
state takes
Safety_Period
-
Ignit_Period
.
Flame out too late
If at the end of the
Post purge
0 state the flame is still detected a lockout follows.
Flame loss
When a flame is lost during a burn cycle the control will restart the boiler once. At
the second flame loss the boiler will stop and blocking mode follows. The number of
restarts is limited by the
Max_Flame_Trials
setting. (Default set to 1)
Fan supervision
The fan speed is continuously monitored.