8
3 TECHNICAL DATA FOR S-CBX BOILERS
3.1 Functional introduction
The S-CBX boilers are central heating boilers with a maximum high efficiency. Such a performance can be reached
by, amongst other things, using a special heat exchanger made of stainless steel. This allows the flue gases to cool
down below the condensation point, and so release extra heat. This has an immediate positive impact on the
efficiency.
The S-CBX boiler is standard set for Natural Gas (G20).
Fuel used should have sulphur rates with a maximum annual peak over a short period of time of 150 mg/m
3
and an
annual average of 30 mg/m
3
.
Boiler control includes:
▪
Cascade control for up to sixteen boilers.
▪
Remote operation and heat demand indication from each boiler.
▪
Weather compensation control.
▪
Calorifier control.
Connections for:
▪
On/Off thermostat.
▪
0-10 VDC remote flow temperature (set point)
control.
▪
0-10 VDC remote burner input control.
▪
Outdoor temperature sensor.
▪
External calorifier pump or diverter valve.
▪
Boiler pump.
▪
PWM control for external boiler pump.
▪
System pump.
▪
External flow switch or external safety device.
▪
Modbus.
▪
External system sensor.
▪
DHW indirect sensor or DHW control thermostat.
▪
Touchscreen.
▪
External Ignition transformer.
3.2 Location of version numbers
Burner Controller Hardware Version
– To be found on the second line of the white sticker on the side of the burner controller.
e.g. 957MN15_3Rh4a
Burner Controller Software Versions
– Press the menu button , go to Information and then to Software Versions.
Information
Software Versions
Boiler Status
Boiler History
Error Log
i
Software Versions
Display [63EF 83BC]
Boiler [5C79 14A9]
Device Group 900MN
Summary of Contents for S-CBX 105