Quick Stopping Burners:
If the T_System is Hyst_Up_Quick_Stop degrees above the Cascade_Setpoint, the
burners are stopped at intervals of
Quick_Stop_Next_Depending_Delay
, for example
30 sec.
Starting and Stopping Burners
With a small difference between T_System and the Cascade_Setpoint the call for a start or stop of respectively
the next or last depending burner is executed.
•
Starting Burners
:
If T_System is Hyst_Down_Start_Burner degrees below the Cascade_Setpoint the
burners are started at intervals of Start_Next_Depending_Delay, for example 200 seconds.
•
Stopping Burners:
If T_System is Hyst_Up_Stop_Burner degrees above the Cascade_Setpoint, the
burners are stopped at intervals of Stop_Next_Depending_Delay, for example 180 seconds.
Power balance
When T_System is between Hyst_Down_Start_Burner and Hyst_Up_Stop_Burner a power balance algorithm can
be activated. See Cascade - Power Balance Mode.
Stop all depending
All the depending are stopped as soon as the T_System is way greater than Cascade_Setpoint.
The following graph shows when all the burners are stopped: