SPECIFICATIONS
Input AC parameters on grid
Input voltage range
150 to 265 Vac / 50 to 140 Vac
Input frequency
45 to 65 Hz (auto sensing)
Input current max.
16 Aac (transfer relay)
Output AC parameter off grid
Output voltage
230Vac / 120 Vac* (pure sine wave +/- 2%)
Output frequency
50 Hz/ 60 Hz +/- 0.05% (crystal controlled)
Harmonic distortion
< 2%
Continues power @ 25°C
900 VA
Power 30min. @ 25°C
1,400 VA
Power 3 sec. @ 25°C
2,800 VA
Battery power unit
Battery type
LFP - Lithium Iron Phosphate (LiFePO4)
Nominal battery voltage
48 / 50 Vdc
Nominal capacity
100 Ah
Terminal area
AC output receptacles
2x Hubbell duplex, Hospital spec. grade
AC output fuse
2x thermal – magnetic circuit breaker
AC input connection
ICE 320 - C14 (fuse 10AT)
Interface
CAN (RJ45-8 type “Com bus”)**, USB**
Design and specifications are subject to change without notice.
13
Summary of Contents for S 5000
Page 1: ......