TECHNICAL PASSPORT, INSTALLATION AND MAINTENANCE INSTRUCTION

 

 

ATTENTION! 

Before  installing  and  using  the  heating  boiler,  carefully  read  the 

instruction.  It  will  help  you  correctly  install  and  effectively  use  the  product  while  also 
preventing possible incidents. 

 

 

TECHNICAL SPECIFICATIONS 

 

Solid fuel water heating boiler “Stropuva” (hereafter boiler) designed for various rooms, 

which  are  equipped  with  a central  heating  system, radiator, boilers preparing  domestic  hot 
water,  floor coils, heaters,  or  all  mentioned, heating.  The  system  can  be  with  natural  and 
forced circulation and have an open or closed system. 

 

JSC 

“Stropuva ir ko’’ produces three types of boilers:

 

•  Firewood (firewood);

 

• “U’’ universal (firewood, coal, peat and sawdust briquettes, pellets, wood chips);

 

• “BIO’’ (firewood, sawdust briquettes, pellets, wood chips);

 

with six 7 kW; 10 kW; 12 kW; 

20 kW; 30 kW; 40kW power capacities. Boilers “Stropuva’’ 

can be used to heat premise area ranging from 100 to 400 m

2

.

 

 

1.1 

MAIN TECHNICAL SPECIFICATIONS 

 

Fuel used: firewood, wood residue, sawdust briquettes, peat briquettes, coal, pellets. 

Recommended fuel moisture up to 30 %.

 

Model of boiler

 

 

S7

 

 

S10

 

 

S12

 

 

S20

 

 

S30

 

 

S40

 

S7

 

BIO

 

S10 
BIO

 

S12 
BIO

 

S20 
BIO

 

S30 
BIO

 

S40

 

BIO

 

S10 

U

 

S12 

U

 

S20 

U

 

S30 

U

 

S40

 

U

 

 

Power (kW) *

 

 

7

 

 

10

 

 

12

 

 

20

 

 

30

 

 

40

 

 

7

 

 

10

 

 

12

 

 

20

 

 

30

 

 

40

 

 

10

 

 

12

 

 

20

 

 

30

 

 

40

 

 

Heated area (m

2

) **

 

 

20-70

 

 

50-100

 

 

70-120

 

100-

 

200

 

150-

 

300

 

200-

 

400

 

20-

 

70

 

50-

 

100

 

70-

 

120

 

100-

 

200

 

150-

 

300

 

200-

 

400

 

50-

 

100

 

70-

 

120

 

100-

 

200

 

150-

 

300

 

200-

 

400

 

 

Fuel capacity (dm

3

)

 

 

72

 

 

116

 

 

165

 

 

200

 

 

256

 

 

320

 

 

72

 

 

116

 

 

165

 

 

200

 

 

256

 

 

320

 

 

95

 

 

130

 

 

165

 

 

200

 

 

265

 

 

Maximum firewood amount (kg)

 

 

23

 

 

37

 

 

50

 

 

60

 

 

78

 

 

93

 

 

23

 

 

37

 

 

50

 

 

60

 

 

78

 

 

93

 

 

37

 

 

50

 

 

60

 

 

78

 

 

93

 

 

Maximum pellet amount (kg)

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

50

 

 

80

 

 

105

 

 

130

 

 

180

 

 

220

 

 

80

 

 

105

 

 

130

 

 

180

 

 

220

 

 

Maximum briquette amount (kg)

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

38

 

 

106 

 

141

 

 

170

 

 

222

 

 

264

 

 

54

 

 

141

 

 

170

 

 

222

 

 

264

 

 

Maximum coal amount (kg)

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

-

 

 

67

 

 

95

 

 

116

 

 

149

 

 

176

 

 

Burning time of firewood, 

minimum mode. 

Maximum mode. ***

 

 
 
 

28

 

5,6

 

 
 
 

31,5

 

6,1

 

 
 
 

31.5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

28

 

5,6

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

 
 
 

31,5

 

6,1

 

Burning time of briquettes, 

minimum mode 

Maximum mode ***

 

 

 

-

 

 

 

-

 

 

 

-

 

 

 

-

 

 

 

-

 

 

 

-

 

 

50

 

10

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

 

72

 

14

 

Summary of Contents for BIO S10 U

Page 1: ...STROPUVA TECHNICAL PASSPORT INSTALLATION AND MAINTENANCE INSTRUCTION Solid fuel boiler for central heating...

Page 2: ...ther boiler water heater and floor heating 13 6 3 Connection diagram of Stropuva boiler to another boiler water heater radiator floor heating 14 6 4 Connection diagram of Stropuva boiler to another bo...

Page 3: ...m2 1 1 MAIN TECHNICAL SPECIFICATIONS Fuel used firewood wood residue sawdust briquettes peat briquettes coal pellets Recommended fuel moisture up to 30 Model of boiler S7 S10 S12 S20 S30 S40 S7 BIO S1...

Page 4: ...ound and the chimney mm 991 1413 5 1302 1550 1285 1549 991 1413 5 1302 1550 1285 1549 1494 1302 1673 5 1285 1664 Dimensions mm 1900 1900 1900 1900 1900 1900 h d 1330 450 1900 450 1700 550 2100 550 170...

Page 5: ...arger diameter steel cylinder which provides thermal insulation Heated water resides between these two cylinders There is a draft regulator on the front side of the boiler 2 see 7 3 The construction h...

Page 6: ...rpose is to correctly distribute air in generation zones located below and next to air distributor as well as in combustion zones located near and above the distributor Air distributor 9 Fig 1 rests u...

Page 7: ...at the bottom of the boiler inside the lower doors 11 Fig 1 Fire grates 19 Fig 1 Fig 7 can be found by opening the ash removal doors 11 Fig 1 This part is attached in U boiler for additional air to go...

Page 8: ...boilers from overheating When water pressure reaches critical levels the valve opens up releasing the heated water into the sewerage at the same time adding cold water through the automatic system Va...

Page 9: ...nless steel will have to be used Rectangular liners are not as reliable because openings caused by temperature changes appear at the connections Boiler is placed directly on concrete floor When carryi...

Page 10: ...ple and proven diagrams We don t recommend building accumulative heat tanks because our boiler is more efficient while working in preservation mode than while charging accumulative tank in maximum pow...

Page 11: ...11 TECHNICAL PASSPORT INSTALLATION AND MAINTENANCE INSTRUCTION 6 HEATING SYSTEM DIAGRAM Figure 10 Stropuva...

Page 12: ...warmer than selected value Thanks to this pump P water loudly circulates through coil pipes F of floor heating also flows to boiler through distribution valve T 3 20 50 which when water from radiator...

Page 13: ...atic valve 1 pcs 7 Circulation pump installation kit D25 1 pcs 23 Valve 1 5 bar 1 pcs 8 Separable connection D25 V i 2 pcs F to out of floor heating 9 Automatic bleeding device 1 pcs B to out of water...

Page 14: ...cs 21 Adapter D32 x D25 2 pcs 7 Circulation pump installation kit D25 1 pcs 22 Thermostatic valve 1 pcs 8 Separable connection D25 V i 2 pcs 23 Valve 1 5 bar 1 pcs 9 Automatic bleeding device 1 pcs F...

Page 15: ...lbow D25 x D15 3 pcs 18 Filling valve i i 1 2 1 pcs 7 Circulation pump installation kit D25 8 Separable connection D25 V i 1 pcs 2 pcs 19 Release valve 1 2 20 Brass disc valve V V 1 21 Adapter D32 x D...

Page 16: ...ets and sawdust briquettes immediately ignite so that the load of fuel would not be ignited by leftover ember Before igniting the boiler carefully read the instruction of traction regulator see sectio...

Page 17: ...all down to the bottom Coal load must not be larger than up to the fuel loading door 8 Fig 1 Put firewood about 2 kg on top of coal and ignite it After ignition switch valve 6 Fig 1 must be lifted of...

Page 18: ...disappears see Fig 10 c If fuel is burning well but temperature increases very slowly and there is condensation leaking out of flue it means that the flow of heated water going through boiler is exces...

Page 19: ...ll stick deeper into fuel its lifespan will be reduced significantly Most common installation mistakes Consequences Troubleshooting 1 Installed using other boiler manufacturer diagrams 1 High flow coo...

Page 20: ...diagrams According to Figure 10 we recommend connecting gravity controlled radiator a radiator without thermos valve Hot water goes through balance tap bk1 Fig 10 to the nearest radiator which can wor...

Page 21: ...ts No need to move the boiler and repeatedly connect to the chimney or heating system Usually no need to make changes in the heating system This solutions allows a complete automatization of firing pr...

Page 22: ...fuel boiler STROPUVA 1 pcs Safety pressure valve 1 5 bar 1 pcs Thermometer 1 pcs Deflectors 2 pcs Air injection collector 1 pcs Air distributor 1 pcs Fire grate 1 pcs Technical passport 1 pcs PACKAGE...

Page 23: ...c procedures inspection of boiler and control elements at least once a year To preserve warranty agreement and its entries We recommend that the installation assessment the first start up adjustment o...

Page 24: ...aris Trak distr LT 25144 Lithuania tel 370 525 51763 Boiler model Product number Date of sale Signature Stamp SELLER Date of sale Signature Stamp PERSON RESPONSIBLE FOR INSTALLATION Installation addre...

Page 25: ...e Surname Signature The boiler has a year warranty If the heat exchanger is broken seller has to fix the boiler on its own expense but if other components are broken not due to the fault of the end us...

Page 26: ...JSC Stropuva ir ko company code 300149972 K stu io g 1A Lentvaris Trak distr LT 25144 Tel 370 5 255 17 63 mob 370 656 08961 www stropuva lt info stropuva lt...