3.5.5 Connect the Solarmodules: SOLAR +/- (Only for solar option)
Solar modules are connected on these terminals. Under no circumstances should any other energy
source i.e. wind generator be connected to these terminals! Only solar modules must be connected
with two /-. Depending on the power of the modules, the cable cross section should be
2.5 up to 6mm
2
. Before connecting it is necessary to check with a Voltmeter that the voltage of the
Module meets the following values:
C1312 17-25V/30A, C2324 34 – 45V/30A, C3548 68 – 90V/20A.
3.5.6 Connection to Auxiliary Contact:
On these tree terminals is a potential free change-over contact). The maximal permitted current
and voltage for this is 16A/250Vac. The DEL 5 “Contact active” show the position of them: alight
mind active and off mind non-active. The schematic view of the connections on the front, show the
relay in the non-active mode.
3.5.7 Connection to Remote control:
The Remote Control RCC 01 is connected in the terminal marked „Remote control“ with a RJ11/8
connector. The Remote Control can be plugged IN or plugged OUT during any operation situation.
Push in the connector, without forcing it, until you hear the „click“, now the connector is locked in
place. The same applies to the plug in the Remote Control. The length of the cable for Remote
Control should not exceed 40m. We deliver it with 20m cable.
3.5.8 Connection to Temperature Sensor (Temp.):
The Temperature sensor CT-35 is connected in the terminal marked „Temp“ with a RJ11/6
connector. The Temperature Sensor can be plugged IN or plugged OUT during any operating
situation. Push in the connector without forcing it, until you hear a „click“, now the connector is
locked in place. The Temperature Sensor must be glued to the wall of the battery or near it. The
Temperature Sensor cable must not be tied together with the battery cables or laid in a
rope/bundle.