5.4.3 Example
5.4.3.1 Auxiliary Contact as generator starter
When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is used as a
condition, then you must take note of the following requirements.
If you have to start an emergency back-up supply with a battery having a certain residual capacity,
then two battery levels must be programmed. The first (i.e. Battery 25% LED 17) for the starting or
activating the Auxiliary Contact and the second (i.e. Battery 100% LED15) for stopping or
deactivating the Auxiliary Contact. By programming like this the Auxiliary Contact works with the
lowest set condition and stops when it has reached the highest programmed condition through
charging.
5.4.3.2 Auxiliary Contact as Twilight Switch (With solar charger option)
The Auxiliary Contact of the COMPACT can also be used as a twilight switch , i.e. for operating
automatically the exterior lighting. With it the connected solar modules measure the light intensity.
If the COMPACT is operating without solar modules and a twilight-switching function is desired,
you can connect small solar cells with the nominal voltage of the COMPACT on to the SOLAR
terminals for the purpose of measuring the light intensity. To function as a twilight-switch the
Auxiliary Contact must be programmed so that the condition SOLAR CHARGE (LED 3) is active.
Programming must be carried out in steps and in accordance with the description for the
programming of the Auxiliary Contact.
5.4.4 Manual operating of Auxiliary Contact:
5.5 The Auxiliary Contact can be operated at any time with the Push Button 21
(AUX. CONTACT). The LED 6 „Contact manual“ lights up as information that
the Contact is manually operated, and LED 5 „Contact active“ lights up when
the Contact is active. By pushing the Push Button 21 a second time, the
Contact is deactivated. By pushing it the third time, automatic functions are
restored.
5.5 Disabling some of the compact functions
Each different function charger, inverter and transfer can be disabled. This is useful for specific
applications wtch required to disable some of these tree functions.
If you press the button (20) more than 2 seconds you can have the access to the different
possibilities shown in the following diagram.
In programming mode the display show only the different types of program with the three DEL 2,7
and 9 to each functions. To change the type of programming press shortly the button 20 until your
reach to the right function use according table below. After 10 seconds the COMPACT exit the
programming mode and load the new change.
In user mode, the disabled functions are displayed by blinking LED. So you can see in witch mode
is disabled.