NOTIFICATION SIGNS
The half-power mode has been activated by the manual control.
[
Flashing symbol
]. Monitor mode is activeted.
The AC mains voltage is too low. The battery charger goes into half-power mode.
The message disappears when the mains voltage falls within the nominal range
again. (This indication appears when the battery charger is turned off even under
normal voltage supply conditions).
The battery charger is reducing power because of a high ambient temperature. The
message disappears as soon as the condition which caused the problem is no
longer present. If this message appears frequently check whether the battery
charger has been installed properly.
The temperature measured by the battery sensors (optional) is outside the range
determined for the charge (-20/+55°C). The output voltage of the battery charger
becomes 12.8V (25.6V in the 24V models) so that the batteries are not damaged.
This message disappears when the battery temperature falls back within the cor-
rect range.
CAN BUS communication problem. The system has found a rate of communication
errors which is higher than normal.
If this message appears frequently, check whether the CAN network wiring has
been carried out properly.
NOTIFICATION SIGNS
PROBLEMS WITH AUTOMATIC RESET
Summary of Contents for Innotec MBC 12-25/3
Page 13: ...205 181 90 135 155 75 MBC BATTERY CHARGER DIMENSIONS mm 12 08 2 12 12 2 11 ...
Page 14: ...12 268 244 90 135 155 75 MBC BATTERY CHARGER DIMENSIONS mm 12 25 3 24 12 2 ...
Page 29: ...280 334 272 220 127 MBC BATTERY CHARGER DIMENSIONS mm 12 30 3 12 40 3 27 ...
Page 30: ...28 358 412 272 220 127 MBC BATTERY CHARGER DIMENSIONS mm 12 60 3 24 30 3 ...
Page 45: ...447 495 272 220 127 12 80 3 24 60 3 24 80 3 43 MBC BATTERY CHARGER DIMENSIONS mm ...