STUDER Innotec
Xtender
44 V.3.1.0
User
manual
19
TECHNICAL DATA – XTM
XTM model
1500-12
2000-12
2400-24
3500-24
2600-48
4000-48
Inverter
Rated battery voltage
12V
24V
48V
Input voltage range
9.5 - 17V
19 - 34V
38 - 68V
Continuous power @ 25 °C
1500VA
2000 VA
2000VA
3000 VA
2000VA
3500 VA
Smart
boost
power
1500VA 2000
VA 2400VA 3500
VA 2600VA 4000
VA
30 minute load @ 25 °C
1500VA
2000 VA
2400VA
3500 VA
2600VA
4000 VA
5 second load @ 25 °C
3 x Pcont.
Maximum load
Up to short-circuit
Maximum asymmetrical load Up to Pnom
Load detection (standby)
2 to 25W
Admissible cos phi
0.1 - 1
Maximum efficiency
93%
94%
96%
Idle power OFF/standby/ON
1.2W/
1.4W/8W
1.2W/
1.4W/10W
1.4W/
1.6W/
9W
1.4W/
1.6W/
12W
1.8W/2W
/10W
1.8W/2.1W/
14W
Output voltage
Sin wave 230Vac (+/-2%) / 180-245 Vac or
****Sin wave 120 Vac (+/-2%) / 50-140 Vac
Output frequency
50 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
****60 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
Harmonic distortion
<2%
Overcharge and short-circuit
Automatic disconnection then 2 startup attempts
Overheating protection
Alarm prior to disconnection and automatic restart
Battery charger
6-phase battery charger
Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)
Adjustable charge current
0 - 70A
0 - 100A
0 - 55A
0 - 90A
0 - 30A
0 - 50A
Input current limit
1 - 50A
Maximum input voltage
265Vac / ****150Vac
AC input voltage range
Level detection adjustable from 150 to 230 Vac
****Level detection adjustable from 50 to 140 Vac
Admissible input frequency
45 - 65Hz
(PFC)
EN 61000-3-2
Battery control (factory value / adjustable range with RCC-02)
End of absorption
by duration: 2h / 0.25 - 18 h or by current <10A / 2 - 50 A
Absorption voltage
14.4V/9.5-17V
28.8 / 19 - 34V
57.6 / 38 - 68V
Periodic absorption voltage
- / 9.5 - 17V
- / 19 - 34V
- / 38 - 68V
Floating voltage
13.6V/9.5-17V
27.2 / 19 - 34V
54.4 / 38 - 68V
Reduced maintenance
voltage
- / 9.5 - 17V
- / 19 - 34V
- / 38 - 68V
Equalisation
By number of cycles ( - / - 100) or at fixed intervals ( - / 52 weeks)
End of equalisation
By duration 2h / 0.25 – 10h or by current - / 5 – 50 A
Equalisation voltage
- / 9.5 - 17V
- / 19 - 34V
- / 38 - 68V
Low voltage disconnection
10.8V/9.5- 17V
21.6V/19- 34V
43.2V / 38 - 68V
Reduced floating duration
- / 0 - 32 days
Periodical absorption
- / 0 - 10 hours
Temperature compensation
-5 / 0 to -8mV/°C/Cellule (option BTS-01)
**** concerns -01 model (120Vac range)
Summary of Contents for Xtender BTS-01
Page 2: ......
Page 48: ...STUDER Innotec Xtender 46 V 3 1 0 User manual 20 NOTES ...