18
/11.2015/
G17D
EN
Locate the fan unit in the raised floor first. The di-
stance from the upper edge of the raised floor to
the base should at least be 515 mm.
If the raised floor is higher you can additionally use a
raised floor socket to equalize the height difference.
Place the heat exchanger unit on the raised floor in
front of the cut off for the fan unit.
Both the heat exchanger unit and the fan unit are
equipped with rolls and the corresponding cut offs
in which the rolls of the other unit disappear.
Now push the heat exchanger unit with two persons
from the front onto the fan unit.
Cut-out for rolls of the heat
exchanger unit
Roll in the fan unit