CeilAiR OHS Series Installation, Operation & Maintenance Manual
Air Technology Systems, Inc.
2-15
2.7.3 Optional Equipment
NOTE
All customer provided wiring must be in accor-
dance with local and national electrical code
requirements for Class 2 circuits.
2.7.3.1 Condensate Pump
Systems supplied with a fi eld installed condensate
pump will require power and control wiring to be con-
nected to the unit. The control wires from the terminal
board in the electric box should be run through the
overfl ow switch in the condensate pump housing.
After proper installation of the condensate pump, the
installer must connect two power conductors from
the condensate pump main power terminals to the air
conditioning unit. A ground wire must be connected
to the unit ground stud located within the unit electric
box. Two control conductors must be wired to the
control terminal board located within the unit electric
box. The condensate pump provides pigtail leads for
splice type wire connections with twist on connectors
(wire caps). Refer to the supplied electrical diagram
for proper wire terminations.
2.7.3.2 Remote Temperature Sensor
(See Figures 7 and 8)
The remote temperature sensor requires a three
conductor shielded cable with the shield being termi-
nated at the thermostat. The shield is terminated at
the RS2 thermostat terminal. Both the thermostat and
the sensor provide a terminal strip with box type lugs
for wire connections. Refer to the electrical diagram
supplied for proper wire terminations.
Figure 8- A-Tech-1.2 Control Wiring