38
Cyberair mini Cw originaL instruCtions
EN/06.2021/G23 © STULZ GmbH – all rights reserved
All maintenance work has to be carried out under strict compliance with the country-specific accident pre
-
vention regulations. In particular we refer to the accident prevention regulations for electrical installations,
refrigerating machines and equipment. Non-compliance with the safety instructions can endanger people
and the environment.
Maintenance work is only to be carried out on the units by authorized and qualified specialist staff.
Procedure instructions
• carry out work on the system only when it is shut down.
• switch off the A/C unit at the controller and at the master switch.
• display a „DO NOT SWITCH ON“ warning sign.
• switch off power conducting cables to the unit and secure them against being switched on again.
• check to ensure that they are in the de-energized state.
Note on compliance with DGUV Regulation 3 (DGUV-German social accident insurance)
• Perform a loop impedance or earth measurement after replacing electrical components or safety-relevant
components.
7. Maintenance
7.1 Safety instructions
Component
Maintenance interval
quarterly
half-yearly
yearly
Air circuit
Heat exchanger
x
Fan
x
Air filter
x
Water circuit
Tightness
x
Unit housing
Electrical box
x
Unit interior
x
notiCe
Only use the spare parts listed in the spare parts list. The spare parts list is part of the unit docu
-
mentation enclosed with the unit.
7.2 Maintenance intervals