air side connection
11.3.6 Adapter plate with damper or flexible connection on unit top
Adapter plate with damper
Adapter plate with flexible connection
Damper
• Mount the actuator on the protruding axis of the damper according to the enclosed manufacturer‘s
instructions.
• Mount the damper on the adapter plate with the enclosed screw connections so that the actuator is on the
left and the orange housing is facing backwards.
• Route the cable as shown on the following page.
• Attach the adapter plate to the unit as shown on the previous page.
Flexible duct connection
• Attach the flexible duct connection to the adapter plate with the enclosed screw connections.
• Install an equipotential bonding on the flexible duct connection so that the duct is earthed.
• Attach the adapter plate to the unit as shown on the previous page.
Cabinet size
The hole dimensions F1 and
G1 also apply to the flexible
duct connection.