condensate pump InstRuctIons
Pump data
Volume flow, max.
l/h
Delivery head, max.
m
Power consumption
W
Current consumption
A
Protection degree
Power supply
V
Frequency
Hz
Length
mm
Width
mm
Height
mm
Tank volume
l
Medium temperature, max.
°C
Condensate pump for hot water
The condensate pump is suitable to convey the warm drain water
of a steam humidifier and condensed water, which occurs during
cooling and humidification in air-conditioning units. The operation is
controlled by a float switch depending on the level. An alarm contact
is triggered when the water level inside the pump tank is too high.
Technical data
Installation
The pump must stand horizontally.
• Place the pump in a frost-proof and water-free place.
For Downflow units: in the raised floor
For Upflow units (if there is no raised floor): on the floor next to the air conditioning unit.
Water connection
There are three possible openings for the water inlet: two
on the top of the pump housing and a lateral opening. An
adapter is supplied for this opening, so that a plastic hose
with an internal diameter of 12 mm can be connected.
• Lay a pipe from the condensate drain of the A/C unit
to the water inlet of the pump. The piping must have a
slope.
• Close the openings which are not used.
Water outlet ø10 mm
Water inlet
2x ø40 mm
1x G1“
Pump diagram
Water inlet with adapter