4.5.2 Information Menu Loop
The Info menu screens may be accessed from the Main screen by simply scrolling
with the Up ( ) and Down
( )
arrow keys. The same screens may also be viewed if
you enter the Info menu by pressing the
Prg
key, then the
key. The Info menu
displays screens that provide current temperature "and relative humidity condi-
tions and shows the modes the A/C system is currently operating. There are no
adjustable parameters in this loop. From the Info loop you may view the following
display screens as they apply to the unit confi guration:
MAIN MENU
Factory
INFO
Alarm Log
Press
Enter
(
)
Key
4.5.2.1 Operating Conditions
The fi rst Info screen displays the current Date, Time and provides State of
Operation icons.
The actual control temperature (
°F
) and relative humidity (rh) is always displayed and
the return ("
RetT
"
)
or optional remote supply ("
RSpT
") temperature and dewpoint
(
dp
) will appear, dependant on the T/H sensor selection. The values displayed are
used by the controller to develop control output signals for managing system
operations.
Press ( ) or ( ) Key
01/01/09 00:00:00
00.0°F
00%rh
RetT 00.0°F dp 00.0°F
Unit ON
(Continued on next page)
4.5.2.3
Return Humidity Sensor
Displays the relative humidity as measured by the return T/H sensor inputs. Return
dewpoint is calculated by the controller based on the return T/H sensor inputs and then
shown at the bottom of the display screen.
Press ( ) or ( ) Key
Ret Humidity Sensor
46%rh
return dewpoint 00.0°F
4.5.2.2
Return Temperature Sensor
Displays the air temperature as measured by a return temperature/humidity (T/H) sensor
inputs. The return T/H sensor is factory mounted inside the cabinet.
Press ( ) or ( ) Key
Return Temp Sensor
71.0°F
Press ( ) or ( ) Key
Press ( ) or ( ) Key
Upper Temp Sensor
74.0°F
4.5.2.6 Temperature
Sensors
The temperature screens display the supply air temperature as measured by
sensors located in the cold aisle side of the CyberRow cabinet. The sensors
are located within the cabinet in upper, middle and lower zones as called out
in the display. Values measured by the sensors may be used to individually
control the speeds of the fans (see Section 4.4.4.1).
Press ( ) or ( ) Key
Middle Temp Sensor
72.0°F
Lower Temp Sensor