STULZ CyberRow Chilled Water Series Installation, Operation & Maintenance Manual
(
Dec.
, 2013)
4-32
The table that follows are the Factory default parameters.
Table 1- Factory Default Parameters
PARAMETER
DEFAULT VALUE
UNIT RESPONSE
Temperature Setpoint
72.0° F
CW Prop Band
3.0° F
Controller begins sending proportional signal to CW valve at 72.0°
F. (CW valve starts opening). Proportional control signal ramps up to
100% at 75.0°F. (CW valve is signaled to be 100% open).
CW Int Time
180 sec
Proportional control signal adjusts to deviations in temperature
within 180 seconds.
Dead Band
0.0° F
Controller is proportionally controling CW valve at 72.0°F.
Minimum Fan Speed
25%
Fan motor speed varies between these values when proportionally
controlled.
Maximum Fan Speed
100%
Humidity Setpoint
45% RH
UNIT RESPONSE
Dehumidify Cut-in Offset
+5% RH
CW valve cuts in at 50% RH.
Dehumidify Cut-out Offset
+2% RH
CW valve cuts out at 47% RH.
Dehumidifi cation Fan Speed
60%
Fan motor limited to 60% of maximum speed.
(Note 1)
Humidify Cut-in Offset
-5% RH
Optional humidifi er turns on at 40%RH.
Humidify Cut-out Offset
-2% RH
Optional humidifi er turns off at 43% RH.
Humidifi cation Fan Speed
100%
Fan motor operates at maximum, 100% speed.
(Note 1)
Passwords
DEFAULT VALUE
UNIT RESPONSE
Control
1
When entered, access to Control menu screens is granted
Service
2
When entered, access to Service menu screens is granted
Note 1: Or as limited by max speed setting in Service>Blower menu. See Section 4.5.5.5.
Set Passwords
Control:
1
Service:
2
The second Service>Save Cfg menu screen allows you to
set new passwords for entering the Control and Service
menus.
Service Menu
4.5.5.11 Factory Menu
SERVICE
Save Cfg
FACTORY
Cool
The Factory menu loop may be accessed from the
Service>Factory screen. You must enter the factory level
password to gain access to the loop.