4-42
Factory>Group>Group Status (Screen 8)
Group Status
Running 0
Active 0
Standby 0
Assist 0
Online 0
Out of Service
0
This screen provides an overview of the current duty status for all the A/C units combined in the group.
Display
Description
Variables
Default
Running
Display indicates how many units in the group are
currently operating.
0 to 8
0
Active
Display indicates how many units in the group are
currently active.
0 to 8
0
Standby
Display indicates how many units in the group are
currently in standby.
0 to 8
0
Assist
Display indicates how many units in the group are
currently operating in the capacity assist mode.
0 to 8
0
Online
Display indicates how many units in the group are
currently available to operate.
0 to 8
0
Out of Service
Display indicates how many units in the group are
not available to operate.
-
0
The fi nal step to confi gure a work group is to access the Service>Options>Group Setup screens used to confi gure
parameters that apply to how individual A/C units interact in the work group (see Section 4.6.2.7).
Factory>Group>Plan timing (Screen 9)
Plan timing
Lead unit
1
Plan timer
30
Plan present
Yes
Display
Description
Variables
Default
Lead unit
Display indicates which unit is currently the lead.
0 to 8
0
Plan timer
Display indicates the time delay (in seconds)
between the detection of a communication failure
and the annunciation of a Comm alarm.
0 to 60
30
Plan present
Display indicates if a pLAN is detected by the
controller.
0= No
1= Yes
No