STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
Service Menu
4.5.5.5.4 Custom Setup
From the Service>Options>Custom Setup screen you may press the Enter
(
) key to access a menu loop to set up custom alarm features. Any controller
alarm or signal failure will activate the summary alarm output. Upon receiving
an alarm indication, the user may press the alarm key and call up alarm screen
messages.
Custom Setup
Setup the alarm text,
custom alarms, and
any custom sensors.
CUSTOM
4.5.5.5.5 Customer Alarm Input (Optional)
If enabled, a customer provided alarm input may be used to activate the Summary Alarm relay and show a specifi c
Customer Alarm message in the alarm display screen. A Customer Alarm message may simply be displayed as
"
CUSTOMER ALARM 1
" as shown below, or you may press (
) and use the ( ) and
( ) arrow keys to construct a specifi c
alpha/numeric message in the fi eld stating the specifi c alarm condition in your own terms; i.e. "
GAS DETECTION
",
"
INTRUSION ALARM
", etc. The Customer Alarm message may be set up on one line with up to 20 characters.
Customer Alarm 1
Text
CUSTOMER ALARM 1
4.5.5.5.6 Custom Alarm Setup (Optional)
The
E²
controller may be enabled to activate a Custom Alarm output and energize a designated N.O./N.C. relay. A
custom alarm output is set up by adding the binary bitmask numbers assigned to the specifi c alarms and signal failures
you wish to monitor via the relay and then entering them in the Custom Alarm Setup screen.
Custom Alarm 1 Text
1-8:
8
9-16:
10
17-24:
0
25-32:
16
33-40:
0
41-48:
0
You can select any mix of the 48 alarm variables as shown in the tables that follow. As an example, for a custom alarm
based only on the occurrence of moisture alarm, fi re/smoke, condensate pan, failure of the return humidity sensor you
would enter the following bitmask values for the applicable alarm numbers and enter 0 for the rest:
Custom Alarm number 1 - 8...............Moisture alarm (No. 4) =
8
Custom Alarm number 9 - 16.............Fire/smoke (No. 10) + Condensate pan (No. 12) =
10
(2+8)
Custom Alarm number 25- 32............Return humidity sensor (No. 29) =
16
The custom alarms are set up by entering the bitmask totals developed from the tables on the following page.
4-27
NOTE:
Display screens shown with a dashed border
appear
only if the applicable feature is enabled.
NOTE:
Custom alarm display screens may appear even if the feature
is not enabled. In this case, changes made to these screens will have
no effect.