Installation
STULZ UltraWater 3-stage reverse osmosis system SUW
© STULZ GmbH, Hamburg
- 24 -
1
Connect the hose (blue) to the consumer.
The hose is available as an accessory (1220950).
2
Make sure that the connection to the consumer is
pressure-tight (minimum 4 bar).
3
To disassemble, squeeze the clamping sleeve and
pull off the hose.
7.2.1. Connecting the reverse osmosis water (D)
To connect the supplied pressure hoses, cut the ends of the hoses straight using a sharp pipe cutter.
The components of the supplied connection material are as follows:
• Connecting hose 6 mm (blue)
-
8
-
© STULZ GmbH, Hamburg
-
8
-
1.3 Lieferumfang
Wasserhahn
12 Liter Wasserspeicher
Gehäuseschüssel
Ventil
Zuleitung
Drainageanschluss /
Abflussventil Brauchwasser
Wasseranschlussadapter
Kugelventil
Wasserspeicher
UV-Röhre
Verbindungsschlauch
Proceed as follows to connect the STULZ UltraWater:
The waste water (= concentrate) is expelled from the system with little loss of
pressure. Make sure that the concentrate pipe is NEVER sealed or restricted.
If the concentrate pipe has to be very long (more than 5 meters), the diameter
must also be enlarged accordingly.
The pure water from a reverse osmosis system is completely bacteriological-
ly clean. However, in certain circumstances biofilms may form in the connect
-
ed pure water pipe. To annihilate these or inhibit their formation, a chemical
such as chlorine dioxide can be added to the water. Please contact Technical
Support.
Only use genuine hoses, to ensure tightness.
If the permeate pipe has to be very long (more than 10 meters), the diameter
must also be enlarged accordingly.
Hose
Clamping sleeve