29

 © STULZ GmbH – all rights reserved EN/11.2018/G67C

wib8000 original instructions

Section: Overview

Here you can set the parameters, which will be displayed in the bus overview. 
Up to 20 parameters can be set. The available parameters are shown right.

Section: Bus

The protocol displayed here is automatically determined when the WIB scans 
the bus for units. Only change it in exceptional cases according to the control-
ler type and upon consultation of the Stulz support:

C7000: SCP BMS
C6000: SDC
C5000: SDC
C1002: SDC
C1010/C2020: SCP BMS or SDC (depending on the C1010/C2020 soft-
ware version and the parameters adjusted there)

The adjustable predelay is a delay which is inserted before a command is sent 
to an A/C unit and serves to eliminate interference in bus communication when 
different controller types participate (e.g. C5000 and C7000, in this case the 
predelay must be set for the unit with the C7000).  However, a predelay decel-
erates bus communication.

The adjustable postdelay is a pause after the response of the unit/controller 
has been received. During this time the bus is not used. This parameter serves 
as the predelay to eliminate interference in bus communication. For the individ-
ual case it must be tested which setting is more effective.

In another box you can determine the maximum number of datapoints which is 
transmitted in a command. The value which is displayed here has been adjust-
ed by the WIB due to the detected controller type according to the buffer size 
of the controller. In case of hardware modifications of existing controllers you 
have the possibility to manually adapt the value. 

Meaning of the possibles settings "use addressed request":

No: 

only data package requests are raised. This is appropriate for C7000 IOCs with software version 

IOC-V3.xx and older.

Yes: 

data package requests or addressed requests are raised (automatic selection of the best procedure 

at each request). Only for C7000 IOCs with software version IOC-V4.00 and newer.

Always: only addressed requests are raised. this is necessary for C1010/C2020 controllers with SCP BMS 

protocol.

This parameter is not relevant for the protocol "SDC" (C6000 and older controllers or C1010 with older 
software).

The other menu items (zone, overload start etc.) have already been explained in the context with the zone 
configuration.

Summary of Contents for WIB8000

Page 1: ...Index G67C Issue 11 2018 WIB8000 Original instructions Web Interface Board...

Page 2: ...echnology business spe cialising in A C for data centres and telecommunications installations STULZ has ten production plants 2 in Germany Italy the USA Great Britain Spain 2 in China Brazil and India...

Page 3: ...nts to build up the STULZ bus 11 5 Configuration 12 5 1 Settings forthe service technician 14 5 2 Settings forthe customer 26 6 Operation 34 6 1 Bus view 34 6 1 1 Start window 35 6 2 Menu structure 36...

Page 4: ...gs Connection to the internet The WIB8000 Web Interface Board may not be connected directlyto the internet but must be protected by a firewall or a VPN tunnel So choose an IP address forthe WIB from t...

Page 5: ...ntrol of A C units On the operators s side the appropriate hardware PC or server and the appropriate software SNMP client and orweb browser are necessary The STULZ controllers in A C units are sequent...

Page 6: ...citive grounding The voltage free input can be used to send an e mail with up to 255 characters when the voltage at this input rises from 0 to at least 9V or drops from at least 9Vto 0V Setting at the...

Page 7: ...larm on at least one controller blinks internal WIB alarm e g e mail cannot be sent such an alarm is shown in the eventlog but not in the alarm window Function of LEDs Data management of up to 2x 32 S...

Page 8: ...the front Note In chillers with a C6000 no sequencing at the chiller itself may be activated when a WIB8000 connection exists or is planned Otherwise a communication with the WIB8000 is not possible a...

Page 9: ...instructions Technical data Supplyvoltage 200 220 230 400 415 460 V CA 10 Frequency 50 60Hz 1 Protection class IP 66 67 UV resistency UL 508 Fire classification UL 94 5V 3 3 WIB8000 in separate box op...

Page 10: ...s is a RS485 bus where up to 32 STULZ controllers can be connected with a WIB The Stulz bus is an RS485 bus with fixed transmission parameters such as baud rate 9600 Baud 8 data bits etc Following val...

Page 11: ...CPU addr C1002 Menu point CPU Address chosen with arrow keys C4000 Ring C configuration interface C1010 see C1010 manual C2020 see C2020 manual In case of a controller supervisor combination the foll...

Page 12: ...bythe customer Forthis connect the WIB8000 to your PC laptop first and configure the WIB The adjusted parameters are updated after a WIB8000 reboot To connect the WIB8000 to your PC laptop the followi...

Page 13: ...ion and to finish the dialogue Moving the cursor on this icon opens a menu in which you can select whetherto displaythe units by bus or by zone participation Choosing the bus view a submenu is display...

Page 14: ...then with the cycle ofthe adjusted interval The following parameters have to be adjusted Avalid NTP server address server name or IP address two time intervals hourly daily weekly and the relative tim...

Page 15: ...ications are effective only after a reboot ofthe WIB You can comfortably reboot the WIB by clicking on the menu item reboot in the menu WEB INTERFACE The indication of a DNS address only IP address po...

Page 16: ...il systems which accept messages without this field but which on the other side reject messages which do have this field containing a not plausible date Forthis reason this function should only be ena...

Page 17: ...e community which has write access Trap There are the following settings for specifying the unit name in the SNMP message Standard the designation is automatically generated following the pattern bus...

Page 18: ...acc to list 1 1 1 1 1 1 1 1170 example unit temperature bus number 1 or 2 WIB8000 bus bywhich the unit is connected global address 0 to 65535 adjusted at the unit module number 1 to 6 always 1 for C70...

Page 19: ...et the time how long the WIB waits for a response of connected units Exceeding this time is evaluated as a communication error The maximum cache holding time indicates how long data points are availab...

Page 20: ...case if a unit controller can not be provided with voltage at the time By menu item create unit in the menu Web Interface bus you have the possibilityto manually create units By menu item delete unit...

Page 21: ...selection influences the number of represented parameters the same as the protocol volume and the unit commands which are used forthe communication between WIB and the unit controller 4 type MC MSC th...

Page 22: ...00 C6000 You can define 20 zones maximum The WIB zones 15 20 can be used for C7000 IOCs which are also assigned to a C7000 IOC zone This may be necessary e g in case of DFC control and a simultaneous...

Page 23: ...sta ble in the section Emergency operation and the additional unit start by overload adjustable in menu Con fig Web Interface section overload start will further be functioning The assignment of units...

Page 24: ...n IOC which has already been assigned to a WIB zone before is added to an IOC zone by IOC orAT this IOC is removed from the WIB zone as soon as the WIB detects it An IOC zone can only be configured fo...

Page 25: ...our settings are available Overload start An overload start for a unit forwhich you adjust this is carried out ifthe adjusted temperature is exceeded or if the adjusted humidity is higherthan the meas...

Page 26: ...in the language ofyour country The default language is also valid for all emails automatically sent as fortheir attachment Datalog Using the datalog function you can have e mails sent to yourself in...

Page 27: ...h the time controlled sequencing HTTP You can have displayed a freely selectable logo in the top right corner of each page In the choice box source you can enterthe path which describes the location w...

Page 28: ...eliminarily receives an automatically generated designation Section Datalog With the datalog function you can record the chronological course of single measured values Up to five measured values perA...

Page 29: ...d During this time the bus is not used This parameter serves as the predelayto eliminate interference in bus communication Forthe individ ual case it must be tested which setting is more effective In...

Page 30: ...limit the time space to be displayed by selecting the appropriate menu item The following items are available 1 all 2 last hour 3 last 24 hours 4 last 7 days last always in the meaning of recent Vert...

Page 31: ...31 STULZ GmbH all rights reserved EN 11 2018 G67C wib8000 original instructions Info Data Datalog Example Note For a better presentation a record from a non air conditioned room has been used here...

Page 32: ...the days at which this shall happen individuallyfor each receiver for several days by mouseclick while keeping the Ctrl key pressed The time spaces can also be set specificallyfor each receiver SMS no...

Page 33: ...contacts changes in a waythat 9V are exceeded or are passed under an e mail will be sent to an adjustable address The e mail will contain the text in the input box following 0V when 9V at the auxilia...

Page 34: ...ered bythe tab WIB8000 Bus 1 The start point when setting unit parameters via the WIB module is the bus view or if existant the zone view Bythe bus viewthe parameterwhich characterize the unit and giv...

Page 35: ...d typing the newvalue The modification will be effective when you confirm it by clicking on the Send button By clicking on the Unit name in the bus view you get to the start window ofthe selected unit...

Page 36: ...e displays three main menus Info Operate and Config In the menu line for controllers which can control several modules the single modules are displayed module 1 module 2 etc the above mentioned struct...

Page 37: ...37 STULZ GmbH all rights reserved EN 11 2018 G67C wib8000 original instructions Config menu...

Page 38: ...38 EN 11 2018 G67C STULZ GmbH all rights reserved wib8000 original instructions 6 2 2 Menu structure for chillers with C7000 Info menu Operate menu Config menu...

Page 39: ...39 STULZ GmbH all rights reserved EN 11 2018 G67C wib8000 original instructions Info menu Operate menu Config menu 6 2 3 Menu structure for chillers with C6000...

Page 40: ...1 2 1 1 2 0 1 3 6 1 4 1 29492 10 sysObjectID OID 1 3 6 1 2 1 1 5 0 WIB 8000 SNMP Interface sysName OID 1 3 6 1 2 1 1 6 0 aircondition sysLocation 2 Speed Considerthe notes on bus configuration Timeout...

Page 41: ...wse button choose the newfirmware image file which you downloaded before from the e Stulz area ofthe Stulz website on the hard disk ofyour PC Use the Send button to transferthis file from the PC to th...

Page 42: ...lowing message is displayed in the state section Firmware image damaged Please upload new image In this case the image must be uploaded again onto the WIB8000 The WIB8000 restart bythe web page is blo...

Page 43: ...ot connected Disconnecting the battery could be reasonable for an intermediate storage to save the battery capacity This jumper is not set at delivery JumperJ1 for battery connection A battery change...

Page 44: ...that the WIB8000 can not be reached via the LAN anymore you can reset the WIB to the factory setting by a jumper on the board The steps in detail switch offthe WIB open the box set jumperJ5 close the...

Page 45: ...e information about the occurred alarms and the equipment ofthe system The menu item event log records all alarms the same as WIB event messages the menu item overview shows the hardware version ofthe...

Page 46: ...d it to the technical support of Stulz These files automatically receive the file name ioceventlog csv Ifyou download several parts think of rena ming the files as e g ioceventlog_part1 csv When the e...

Page 47: ...at the site there is the possibilityto connect the WIB8000 to the telephone net work by a MoRoS router WIB8000 and MoRoS router must be connected by a 1 1 Ethernet patch cable the MoRoS router establ...

Page 48: ...ction with the MoRoS router does not differfrom the configuration in a normal network so that this can be carried out according to the WIB8000 manual Network Setup The parameters ofthe IP net can be s...

Page 49: ...een under 11 2 6 ofthe manual The check mark enable NAT must be set default To confirm click on OK at the end ofthe page After having finished these settings the WIB8000 should be accessible bythe tel...

Page 50: ...GEST MD5 CRAM MD5 LOGIN PLAIN AUTO Sender ____________________ max 64 characters ____________________ 4 SNMP 1st part Read community _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ max 20 characters Write com...

Page 51: ..._ _ _ max 20 characters IP address server name _ _ _ _ _ _ _ _ _ _ _ _ port _ _ _ _ _ max 5 numerals Trap receiver 6 Community _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ max 20 characters IP address ser...

Page 52: ...x netherlands STULZ GROEP B V Tel 31 20 54 51 111 Fax 31 20 64 58 764 stulz stulz nl new zealand STULZ New Zealand Ltd Tel 64 9 360 32 32 Fax 64 9 360 21 80 sales stulz co nz poland STULZ Polska SP Z...

Reviews: