4.5. Protection components of the refrigerant circuit
Refrigerant filter
A chiller filter is located in the liquid line of each refrigerant circuit. This filter holds the humidity particles in the chiller.
Evaporator antifreeze protection device.
The antifreeze protection device prevents the evaporator from freezing.
An evaporator outlet probe placed on the water circuit measures the temperature of the cooled liquid. If this reaches
values equal to or lower than the alarm threshold, the control disables the cooling mode.
4.6. Hydraulic diagrams
Key
Name, symbol
Meaning
Name, symbol
Meaning
EV
Evaporator
RE
Heater
LE
Electric level
RI
Filling cap
LV
Visual level
S
Temperature probe
MN
Pressure gauge
TS
Maximum thermostat
MT
Electric motor
VA
Tank
PW
Water pump
VS
Tank discharge
PD
Differential pressure switch
See water-refrigeration diagram “Refrigerant diagrams” on page 20