5.2. Technical data
(1) Nominal conditions
MODEL
STANDARD
Temperature of the fluid to be cooled at the evaporator inlet
[°C]
20
Temperature of the fluid to be cooled at the evaporator outlet
[°C]
15
Condenser outside air temperature [°C]
32
Refrigerant (composition referred to the weight)
Water 100%
(2) The sound pressure level is measured according to Standard EN-ISO 9614-1, and declared at the following
conditions:
•
in free field
•
with unit positioned on a reflective base
•
with unit running under nominal conditions.
The sound pressure level declared considers the contribution of the standard circulation pump.
(3) Inrush current =compressor inrush c fan maximum operating c pump maximum operating current
If glycol is added to the liquid to be cooled, the technical data stated in this paragraph must be
corrected according to the coefficients indicated in the following table
Percentage of ethylene glycol
Percentage of propylene glycol
10%
20%
30%
10%
20%
30%
Freezing temperature
[°C]
-3.9
-8.9
-15.6
-3.3
-7.8
-12.2
Cooling capacity
Corrective
coefficients
on
technical
sheet data
0.997
0.990
0.984
0.993
0.985
0.974
Power consumption
0.999
0.997
0.996
0.999
0.996
0.993
Flow rate of the fluid to be
cooled
1.014
1.033
1.068
0.989
1.009
1.017
Load loss from the side of the
fluid to be cooled.
1.07
1.16
1.30
1.04
1.14
1.23