EN/
0915/WLA Compact
/34
WLA-WLL 34
WLA-WLL 44
MAIN
Cooling capacity
(1)
W
3400
4400
Sound pressure level at 1 m
(1) (2)
dB(A)
55
55
Refrigerant
R134a
R134a
N. of refrigerant circuits
1
1
Nominal power supply
V/-/Hz
230/1/50
230/1/50
Maximum power consumption with standard pump
W
3600
4300
Maximum current consumption with standard pump
A
16.1
20.9
Inrush current with standard pump
(3)
A
53
67
Weight for transport
kg
92
99
Weight in operation
kg
113
120
Height
mm
530
530
Width
mm
800
800
Depth
mm
615
615
COMPONENTS
COMPRESSOR
N°
1
1
Type of compressor
scroll
scroll
Maximum power consumption
kW
2450
3150
Maximum current consumption
A
10
14.8
Inrush current
A
47
61
AXIAL FAN
N°
1
1
Fan diameter
mm
Ø 300
Ø 300
Air flow rate with free inlet
m
3
/h
3410
3410
Power consumption
W
230
115
Current consumption
A
1.1
1.1
EVAPORATOR
Flow rate of the fluid to be cooled
(1)
l/min
9.7
12.5
Load loss from the side of the fluid to be cooled
(1)
kPa
2.68
4
STORAGE TANK
Tank capacity
l
20
20
PUMP
Maximum power consumption
W
920
920
Maximum current consumption
A
5
5
Maximum head
kPa
600
600
(1)
Values referred to:
- return fluid temperature: 20°C
- supply fluid temperature: 15°C
- External air temperature: 32°C
(2)
Sound pressure level measured according to EN-ISO 9414-1
(3)
Inrush current =compressor inrush c fan maximum operating c operating pump maximum current
(4)
standard circuit without accessories Fluid: pure water
St
andar
d t
echnical sheet.
Chec
k on
MANU
AL P
AR
T II
for an
y modif
ication.