SZ-81145

Sr.No. 

Description of parameters and functions.

Parameter setting

 method. 

Parameter

Parameter List

Min : MINIMUM  Max : MAXIMUM
Fact. Set : FACTORY SETTING(DEFAULT)

Use Down/Prg key to enter program mode,

Use Up, down, set keys to change values of parameters.  

P2

01

press set key.

To change the parameter value, Use UP/DOWN keys to set desired 

range.

Range

Min 

Max 

   Fact. Set 

P3+1.0

0

99.9 C

0

99.9 C

Function: To set maximum allowable high 
temperature limit and alarm.

Example:

  Setting  this  parameter  at 

0

99.9 C  will  not  allow  the  set  point  to  go 

0

 

above  99.9 C. Also  if  the  temperature 

0

 

reaches or goes above 99.9 C.the display 
will show High Temp. Alarm & at this point 
the alarm will activate.

Once set at a particular range, this will 
not allow the set point to go above this 
range.

P3

02

press set key.

To change the parameter value, Use UP/DOWN keys to set desired 

range.

Range

Min 

Max 

   Fact. Set 

0

-50 C

P2-1.0

0

-50 C

Function: To set minimum allowable low 
temperature limit and alarm.

0

-50 C. Also, if the temperature reaches or 

0

goes below -50 C   the display will show 

 

Low  Temp.  Alarm and  at  this  point  the 
alarm will activate.

Once set at a particular range, this will not 
allow the set point to go above this range.

0

Example: 

Setting this parameter at -50 C  

will not allow the set point to go below 

O

Note : Below -9.9 C, resolution automatically 

O

change to 1 C .

04

SZ-81145

Use UP/DOWN keys to set desired 
range.

 

0

Example:

 If the set point is set at 10.0 C 

 

0

and differential is set as 2.0 C, then when 

0

 

t h e   s y s t e m   r e a c h e s   1 0 . 0 C , t h e

 

compressor   will cutout. Since differential 

0

  

 

is 2.0 C, the compressor will cut in(restart) 

0

0

0

at 12.0 C (10.0 C + 2.0 C).

press set key.

To change the parameter value,

03

0.5ºC

20.0ºC

2.0ºC

Range

Min 

Max 

   Fact. Set 

P4

Function: To set differential for 
temperature.

Use UP/DOWN keys to set desired 
value.

Function: To set temperature probe 
calibration.

P5

press set key.

To change the parameter value,

04

Range

Min 

Max 

   Fact. Set 

-9.9ºC

10.0ºC

0.0ºC

Example:

  If  the  actual  temperature  is 

20.0ºC  and  the  temperature  on  the 
controller  shows  22.0ºC  set  this 

O

parameter to -2.0 C and once out of   this 
mode,  the  temperature  will  display 
20.0ºC.  (22.0ºC-2.0ºC).

H2

05

To change the parameter value,
press set key.

Use UP/DOWN keys to set desired 
range.

Range

Min 

Max 

   Fact. Set 

H3+1

100%

100%

Function: To set maximum allowable high 
alarm limit relative Humidity.

Once set at a particular range, this will not 
allow the set point to go above this range.

Example:

 Setting this parameter at 100% 

will  not  allow  the  set  point  to  go  above 

 

100%.Also if the humidity reaches or goes 

 

above  100%. the  display  will  show  High 
humidity Alarm  &  at  this  point  the  alarm 
will activate.

Sr.No. 

Description of parameters and functions.

Parameter setting

 method. 

Parameter

Summary of Contents for SZ-81145

Page 1: ...User Manual SZ 81145 INDIA www pvrcontrols com RH TEMPERATURE INDICATOR...

Page 2: ...ifferential for temperature Temperature probe calibration 04 H2 H3 05 Maximum allowable high humidity limit and alarm Minimum allowable low humidity limit and alarm Suggested Connection Diagram Panel...

Page 3: ...e set point to go below O Note Below 9 9 C resolution automatically O change to 1 C 04 SZ 81145 Use UP DOWN keys to set desired range 0 Example If the set point is set at 10 0 C 0 and differential is...

Page 4: ...wer ON display setting 0 temperature When E0 set to 2 and E1 is 0 then E1 value set to 10 sec default 1 RH 2 temperature RH 06 SZ 81145 Sr No Description of parameters and functions Parameter setting...

Page 5: ...re default settings of the controller When set to 1 all parameters are programmed to factory settings Used to debug setting related problems Ht Lt Fault Messages Message Parameter Description High tem...

Page 6: ...2 13 14 16 17 18 20 RH 12V IN GND PROBE RESET KEY ALARM C NC NO 10VAC BUZZER PHASE NEUTRAL ALARM 5A 250VAC To SZ B75 10Vdc 10mA max To SZ N75 Caution Wiring for 230Vac Loads Only 10 SZ 81145 Panel Cut...

Page 7: ...mages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain...

Page 8: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Reviews: